2008-11-04 10:06:25PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. PLEASE CLEARLY INDICATE THE BUILDING CLASSIFICATION
 AND OCCUPANCY LOAD ON THE PLANS.
 PER FBC BUILDING SECTION 302.1 GENERAL. STRUCTURES OR
 PORTIONS OF STRUCTURES SHALL BE CLASSIFIED WITH RESPECT
 TO OCCUPANCY IN ONE OR MORE OF THE GROUPS LISTED BELOW.
  
 A} ASSEMBLY (SEE SECTION 303): GROUPS A-1, A-2, A-3,
 AND A-5
  
 B} BUSSINESS (SEE SECTION 304): GROUP B
  
 C} EDUCATIONAL (SEE SECTION 305): GROUP E
  
 D} FACTORY AND INDUSTRIAL (SEE SECTION 306): GROUPS F-1
 AND F-2
  
 E} HIGH HAZARD (SEE SECTION 307) GROUPS H-1, H-2, H-3,
 H-4, AND H-5
  
 F} INSTITUTIONAL (SEE SECTION 308): GROUP I-1, I-2, AND
 I-3
  
 G} MERCANTILE (SEE SECTION 309): GROUP M
  
 H} RESIDENTIAL (SEE SECTION 310): GROUPS R-1, R-2, R-3
 AS APPLICABLE IN SECTION 101.2, AND R-4
  
 I} STORAGE (SEE SECTION 311): GROUPS S-1 AND S-2
  
 J} UTILITY AND MISCELLANEOUS (SEE SECTION 312): GROUP U
  
 K} DAY CARE (SEE SECTION 313): GROUP D
  
 *NOTE: THIS APPEARS TO BE A STORAGE FACILITY. PLEASE
 KNOW THAT FOR A STORAGE FACILITY PER THE FBC-2004
 PLUMBING TABLE 403.1 MINIMUM NUMBERS OF REQUIRED
 PLUMBING FIXTURES FOR A S-1 OR S-2 OCCUPANCY ARE THE
 FOLLOWING.
  
 *WATER CLOSETS= 1 PER 100.
 *LAVATORIES= 1 PER 100.
 *DRINKING FOUNTAIN= 1 PER 1000.
 *OTHER= 1 SERVICE SINK.
  
 PLEASE INDICATE ON THE RESUBMITTED PLANS THAT THE
 FACILITY HAS AN EXISTING DRINKING FOUNTAIN AND SERVICE
 SINK OR PROVIDE SAID FIXTURES ACCORDINGLY. PLEASE KNOW
 THAT THE DRINKING FOUNTAIN SHALL BE ACCESSIBLE PER THE
 FBC-2004 CHAPTER 11, FLORIDA ACCESSIBILITY CODE
 SECTIONS.
  
 **11-4.15 DRINKING FOUNTAINS AND WATER COOLERS
 (ELAVATION DETAIL REQUIRED WITH THE FOLLOWING
 INFORMATION)
 11-4.15.2 SPOUT HEIGHT. SPOUT HEIGHT 36" TO OUTLET
 MAXIMUM.
 11-4.15.3 SPOUT LOCATION. FRONT OF UNIT, WATER FLOW IN
 TRAJECTORY THAT IS PARALLEL OR NEARLY PARALLEL TO FRONT
 OF THE UNIT, WATER FLOW MINIMUM OF 4" HIGH. ON AN
 ACCESSIBLE OVAL OR ROUND BOWL FLOW OF WAER IS WITHIN 3"
 OF THE FRONT OF FOUNTAIN.
 11-4.15.4 CONTROLS. SHALL BE FRONT MOUNTED OR SIDE
 MOUNTED NEAR FRONT EDGE.
 11-4.15.5 CLEARANCES. KNEE 27" HIGH, & 30" X 48" FLOOR
 SPACE.
 11-4.1.3(10)(A) WHERE ONLY ONE DRINKING FOUNTAIN IS
 PROVIDED ON A FLOOR, THERE SHALL BE A DRINKING FOUNTAIN
 WHICH IS ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS
 IN ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE
 TO THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.(THIS
 CAN BE ACCOMMODATED BY THE USE OF A HI-LO FOUNTAIN OR
 BY SUCH OTHER MEANS AS WOULD ACHIEVE THE REQUIRED
 ACCESSIBILITY FOR EACH GROUP ON EACH FLOOR).
  
 2. CLEARLY INDICATE THE CODE CYCLE ON THE PLANS. PER
 CITY OF WPB AMENDMENTS TO CHAPTER 1, SECTION 106.1.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 THE CURRENT CODE CYCLE FOR THE PLANS IS "FBC-2004 WITH
 2007 REVISIONS"
  
 END OF COMMENTS:
  
 *PLEASE CALL IS THERE ARE ANY QUESTIONS.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]