2008-11-04 10:06:25 | PLUMBING PLAN REVIEW: |
| DENIED: |
| |
| PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| |
| 1. PLEASE CLEARLY INDICATE THE BUILDING CLASSIFICATION |
| AND OCCUPANCY LOAD ON THE PLANS. |
| PER FBC BUILDING SECTION 302.1 GENERAL. STRUCTURES OR |
| PORTIONS OF STRUCTURES SHALL BE CLASSIFIED WITH RESPECT |
| TO OCCUPANCY IN ONE OR MORE OF THE GROUPS LISTED BELOW. |
| |
| A} ASSEMBLY (SEE SECTION 303): GROUPS A-1, A-2, A-3, |
| AND A-5 |
| |
| B} BUSSINESS (SEE SECTION 304): GROUP B |
| |
| C} EDUCATIONAL (SEE SECTION 305): GROUP E |
| |
| D} FACTORY AND INDUSTRIAL (SEE SECTION 306): GROUPS F-1 |
| AND F-2 |
| |
| E} HIGH HAZARD (SEE SECTION 307) GROUPS H-1, H-2, H-3, |
| H-4, AND H-5 |
| |
| F} INSTITUTIONAL (SEE SECTION 308): GROUP I-1, I-2, AND |
| I-3 |
| |
| G} MERCANTILE (SEE SECTION 309): GROUP M |
| |
| H} RESIDENTIAL (SEE SECTION 310): GROUPS R-1, R-2, R-3 |
| AS APPLICABLE IN SECTION 101.2, AND R-4 |
| |
| I} STORAGE (SEE SECTION 311): GROUPS S-1 AND S-2 |
| |
| J} UTILITY AND MISCELLANEOUS (SEE SECTION 312): GROUP U |
| |
| K} DAY CARE (SEE SECTION 313): GROUP D |
| |
| *NOTE: THIS APPEARS TO BE A STORAGE FACILITY. PLEASE |
| KNOW THAT FOR A STORAGE FACILITY PER THE FBC-2004 |
| PLUMBING TABLE 403.1 MINIMUM NUMBERS OF REQUIRED |
| PLUMBING FIXTURES FOR A S-1 OR S-2 OCCUPANCY ARE THE |
| FOLLOWING. |
| |
| *WATER CLOSETS= 1 PER 100. |
| *LAVATORIES= 1 PER 100. |
| *DRINKING FOUNTAIN= 1 PER 1000. |
| *OTHER= 1 SERVICE SINK. |
| |
| PLEASE INDICATE ON THE RESUBMITTED PLANS THAT THE |
| FACILITY HAS AN EXISTING DRINKING FOUNTAIN AND SERVICE |
| SINK OR PROVIDE SAID FIXTURES ACCORDINGLY. PLEASE KNOW |
| THAT THE DRINKING FOUNTAIN SHALL BE ACCESSIBLE PER THE |
| FBC-2004 CHAPTER 11, FLORIDA ACCESSIBILITY CODE |
| SECTIONS. |
| |
| **11-4.15 DRINKING FOUNTAINS AND WATER COOLERS |
| (ELAVATION DETAIL REQUIRED WITH THE FOLLOWING |
| INFORMATION) |
| 11-4.15.2 SPOUT HEIGHT. SPOUT HEIGHT 36" TO OUTLET |
| MAXIMUM. |
| 11-4.15.3 SPOUT LOCATION. FRONT OF UNIT, WATER FLOW IN |
| TRAJECTORY THAT IS PARALLEL OR NEARLY PARALLEL TO FRONT |
| OF THE UNIT, WATER FLOW MINIMUM OF 4" HIGH. ON AN |
| ACCESSIBLE OVAL OR ROUND BOWL FLOW OF WAER IS WITHIN 3" |
| OF THE FRONT OF FOUNTAIN. |
| 11-4.15.4 CONTROLS. SHALL BE FRONT MOUNTED OR SIDE |
| MOUNTED NEAR FRONT EDGE. |
| 11-4.15.5 CLEARANCES. KNEE 27" HIGH, & 30" X 48" FLOOR |
| SPACE. |
| 11-4.1.3(10)(A) WHERE ONLY ONE DRINKING FOUNTAIN IS |
| PROVIDED ON A FLOOR, THERE SHALL BE A DRINKING FOUNTAIN |
| WHICH IS ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS |
| IN ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE |
| TO THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.(THIS |
| CAN BE ACCOMMODATED BY THE USE OF A HI-LO FOUNTAIN OR |
| BY SUCH OTHER MEANS AS WOULD ACHIEVE THE REQUIRED |
| ACCESSIBILITY FOR EACH GROUP ON EACH FLOOR). |
| |
| 2. CLEARLY INDICATE THE CODE CYCLE ON THE PLANS. PER |
| CITY OF WPB AMENDMENTS TO CHAPTER 1, SECTION 106.1.1 |
| INFORMATION ON CONSTRUCTION DOCUMENTS. |
| THE CURRENT CODE CYCLE FOR THE PLANS IS "FBC-2004 WITH |
| 2007 REVISIONS" |
| |
| END OF COMMENTS: |
| |
| *PLEASE CALL IS THERE ARE ANY QUESTIONS. |
| |