Plan Review Notes For Permit 08100531 |
Permit Number |
08100531 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-11-03 14:35:49 | *****DENIED***** | | | | | | 01. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | 02. THE 2003 EDITION OF NFPA 101 SHALL BE REFERENCED. | | | | 03. PLEASE LIST THE FOLLOWING INFORMATION FOR THIS | | OCCUPANCY: * OCCUPANT LOAD AND EGRESS CAPACITIES * IS | | THERE A FIRE ALARM SYSTEM? * IS THERE A FIRE SPRINKLER | | SYSTEM? | | | | 04. PROVIDE AN EXISTING FLOOR LAYOUT OF THE TENANT | | SPACE. | | | | 05. WHAT EQUIPMENT AND/OR PROCESSES WILL BE USED AT THE | | NEW MEZZANINE LEVEL? | | | | 06. STAIRS SHALL COMPLY WITH 7.2.2 OF NFPA 101 - 2003 | | EDITION. | | | | 07. PROVIDE THE PRESCRIPTIVE STRENGHTS FOR THE NEW | | HANDRAILS. | | | | 08. THE STAIRS SHALL HAVE HANDRAILS ON BOTH SIDES AND | | SHALL BE CONTINUOUSLY GRASPABLE ALONG THEIR ENTIRE | | LENGHT. | | | | 09. EXPLAIN THE STAIR'S 14 RISERS @ 7-5/8" AND ITS 13 | | TREADS @ 10" AS LISTED IN THE STAIR DETAIL. | | | | 10. SHOW THE LOCATION OF EXIT LIGHTS, EMERGENCY LIGHTS, | | AND FIRE EXTINGUISHER(S) FOR THE NEW FLOOR PLAN. | | | | 11. SPECIFY THE INTERIOR WALL AND CEILING FINISH | | MATERIALS FOR THE NEW OFFICES IN TERMS OF CLASS A, | | CLASS B, OR CLASS C. | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING WHERE THE COMMENT WAS ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|