| ** DENIED REVIEW ** |
| |
| 1) NOTE: PLEASE INCLUDE NEW OR EXISTING HORNS, STROBES, |
| HORN/STROBE DEVICES MEETING FBC 11-4.28.1, .2 AND .3. |
| PLEASE LIST THE HEIGHTS AND LEVELS. |
| |
| 2) NOTE: PLEASE INCLUDE THE LIGHTING PERFORMANCE |
| CALCULATIONS PER 13-415.2, 13-415.2.ABC.1.1,.1.2. |
| THESE WOULD BE FOR NEW AREAS ONLY AND MAY BE SHOWN ON |
| PLANS FOR TABLE 13-415.2.B |
| PLEASE BE SURE TO COMPLETE THE FIXTURE LEGEND. |
| ** NEW BEING INSTALLED |
| |
| 3) NOTE: PLEASE INCLUDE LIGHTING CONTROLS PER |
| 13-415.1.ABC.1.1, .1.2 AND .1.3. ** NEW BEING INSTALLED |
| ONLY REQUIRED |
| |
| 4) NOTE: THE RISER AS SHOWN ON PLANS IS NOT SHOWN AS IT |
| EXISTS. IF EXISTING THEN PLEASE INDICATE OTHERWISE THE |
| REVIEW WILL BE DONE FOR NEW EQUIPMENT UNDER CURRENT |
| CODES. |
| 230,220,240 ETC |
| |
| 5) NOTE: PLEASE SEE THE CODE SECTION REFLECTED PER |
| 700.12E IS NOW DIFFERENT UNDER THE CURRENT 2005 NEC. |
| THE NEW CODE SECTION IS 700.12F. IF THIS HAD BEEN THE |
| ONLY COMMENT IT WOULD HAVE BEEN REDLINED. PLEASE |
| CORRECT AT THIS TIME. |
| |
| 6) NOTE: PLEASE SEE THE PLANS NEED TO STATE THE |
| FOLLOWING CODES AS A DESIGN STANDARD AT A MINIMUM. |
| THESE ARE FOR THIS REVIEWER ONLY. PLEASE BE AWARE OF |
| ANY COMMENTS FORM OTHER TRADES WHICH MAY HAVE ANY |
| COMMENTS |
| |
| 2004 FBC W/2007 REVISIONS. |
| 2003 NFPA-101 |
| 2005 NFPA-70 |
| |
| 7) NOTE: PLEASE SUBMIT A COMPLETE PANEL SCHEDULE FOR |
| SCOPE OF WORK. AS NO PANEL SCHEDULE WAS SHOWN WITH |
| CIRCUITING LOADS ETC REVIEW OF THESE ITEMS COULD NOT BE |
| DONE. PLEASE INCLUDE THE NEW AND EXISTING LOADS ON |
| PANEL. |
| 220, 408.4, 215.3, 230.42 ETC |
| FBC 106.1.1, .1.2 FOR ADDITIONAL INFORMATION, CLARITY |
| AND COORDINATION. |
| |
| 8) NOTE: PLEASE SUBMIT LIGHTING LEVELS FOR STAIRS UNDER |
| NORMAL AND EMERGENCY CONDITIONS. PLEASE SEE NFPA-101 |
| 7.8.1.3, 7.9.1.2, .2.2. |
| |
| |
| |
| |
| **IMPORTANT** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| INTO TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |