Plan Review Notes
Plan Review Notes For Permit 08100531
Permit Number 08100531
Review Stop E
Sequence Number 1
Notes
Date Text
2008-11-04 08:37:05 
  
  
  
 ** DENIED REVIEW **
  
 1) NOTE: PLEASE INCLUDE NEW OR EXISTING HORNS, STROBES,
 HORN/STROBE DEVICES MEETING FBC 11-4.28.1, .2 AND .3.
 PLEASE LIST THE HEIGHTS AND LEVELS.
  
 2) NOTE: PLEASE INCLUDE THE LIGHTING PERFORMANCE
 CALCULATIONS PER 13-415.2, 13-415.2.ABC.1.1,.1.2.
 THESE WOULD BE FOR NEW AREAS ONLY AND MAY BE SHOWN ON
 PLANS FOR TABLE 13-415.2.B
 PLEASE BE SURE TO COMPLETE THE FIXTURE LEGEND.
 ** NEW BEING INSTALLED
  
 3) NOTE: PLEASE INCLUDE LIGHTING CONTROLS PER
 13-415.1.ABC.1.1, .1.2 AND .1.3. ** NEW BEING INSTALLED
 ONLY REQUIRED
  
 4) NOTE: THE RISER AS SHOWN ON PLANS IS NOT SHOWN AS IT
 EXISTS. IF EXISTING THEN PLEASE INDICATE OTHERWISE THE
 REVIEW WILL BE DONE FOR NEW EQUIPMENT UNDER CURRENT
 CODES.
 230,220,240 ETC
  
 5) NOTE: PLEASE SEE THE CODE SECTION REFLECTED PER
 700.12E IS NOW DIFFERENT UNDER THE CURRENT 2005 NEC.
 THE NEW CODE SECTION IS 700.12F. IF THIS HAD BEEN THE
 ONLY COMMENT IT WOULD HAVE BEEN REDLINED. PLEASE
 CORRECT AT THIS TIME.
  
 6) NOTE: PLEASE SEE THE PLANS NEED TO STATE THE
 FOLLOWING CODES AS A DESIGN STANDARD AT A MINIMUM.
 THESE ARE FOR THIS REVIEWER ONLY. PLEASE BE AWARE OF
 ANY COMMENTS FORM OTHER TRADES WHICH MAY HAVE ANY
 COMMENTS
  
 2004 FBC W/2007 REVISIONS.
 2003 NFPA-101
 2005 NFPA-70
  
 7) NOTE: PLEASE SUBMIT A COMPLETE PANEL SCHEDULE FOR
 SCOPE OF WORK. AS NO PANEL SCHEDULE WAS SHOWN WITH
 CIRCUITING LOADS ETC REVIEW OF THESE ITEMS COULD NOT BE
 DONE. PLEASE INCLUDE THE NEW AND EXISTING LOADS ON
 PANEL.
 220, 408.4, 215.3, 230.42 ETC
 FBC 106.1.1, .1.2 FOR ADDITIONAL INFORMATION, CLARITY
 AND COORDINATION.
  
 8) NOTE: PLEASE SUBMIT LIGHTING LEVELS FOR STAIRS UNDER
 NORMAL AND EMERGENCY CONDITIONS. PLEASE SEE NFPA-101
 7.8.1.3, 7.9.1.2, .2.2.
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  