2008-10-31 17:00:10 | BUILDING PLAN REVIEW |
| PERMIT: 08100531 |
| ADD: 1118 25TH STREET #7 |
| CONT: COMPLETE PROPERTY MANAGEMENT INC. |
| TEL: (561)626-2778 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2007 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 10-31-08 |
| REVIEW: 1ST |
| ACTION: DENIED |
| |
| 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| 2) NOTE: 713.13(6) THE POSTING OF THE NOTICE OF |
| COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST |
| INSPECTION. |
| |
| 3) 2004 FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN |
| OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF |
| ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF |
| THIS CODE. |
| |
| 4) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER |
| JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| BUILDING WITH THE 2007 SUPPLEMENTS. THIS INFORMATION |
| SHALL BE INDICATED ON THE DRAWINGS. |
| |
| 5) THE INFORMATION FOR THE BUILDING IS NOT LEGIBLE |
| 106.1.1. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT |
| CLARITY TO INDICATE THE LOCATION, NATURE & EXTENT OF |
| THE WORK PROPOSED & SHOW IN DETAIL THAT IT WILL CONFORM |
| TO THE PROVISIONS OF THIS CODE AND RELEVANT LAWS, |
| ORDINANCES, AND RULES AND REGULATIONS AS DETERMINED BY |
| THE BUILDING OFFICIAL. INDICATE THE SQUARE FOOTAGE OF |
| THE SPACE AND THE AREA OF THE MEZZANINE. |
| |
| 6) THE DRAWINGS NEED TO CLEARLY INDICATE THE TYPE OF |
| BUILDING PER CHAPTER 6 AND TABLE 503 AND THE USE AND |
| OCCUPANCY PER CHAPTER 3. |
| |
| 7) THE CLEAR HEIGHT ABOVE AND BELOW THE MEZZANINE FLOOR |
| CONSTRUCTION SHALL NOT BE LESS THAN 7 FEET. FBC 505.1 |
| SHOWS COMPLIANCE. THE AGGREGATE AREA OF THE MEZZANINE |
| WITHIN A ROOM SHALL NOT EXCEED ONE-THIRD OF THE AREA OF |
| THE ROOM OR SPACE IN WHICH THEY ARE LOCATED. FBC 502.2 |
| |
| 8) PLEASE INDICATE THE OCCUPANT LOAD OF THE MEZZANINE |
| AND THE ENTIRE SPACE ON THE DRAWINGS PER 505.4 TABLE |
| 1004.1.2 AND TABLE 1607.1 |
| |
| 9) PROVIDE AN EXISTING FLOOR PLAN OF THE EXISTING AREA |
| AND A PROPOSED FLOOR PLAN WITH ALL ELEVATION OF THE NEW |
| AREA INCLUDING THE FRONT AND SIDES ELEVATIONS. |
| |
| 10) 110.4.2 STORAGE & FACTORY- INDUS-TRIAL OCCUPANCIES. |
| IT SHALL BE THE |
| RESPONSIBILITY OF THE OWNER, AGENT, PROPRIETOR OR |
| OCCUPANT OF GROUP S AND GROUP F OCCUPANCIES, OR ANY |
| OCCUPANCY WHERE EXCESSIVE FLOOR LOADING IS LIKELY TO |
| OCCUR, TO EMPLOY A COMPETENT ARCHITECT OR ENGINEER IN |
| COMPUTING THE SAFE FLOOR LOAD CAPACITY. ALL SUCH |
| COMPUTATIONS SHALL BE ACCOMPANIED BY AN AFFIDAVIT FROM |
| THE ARCHITECT OR ENGINEER |
| STATING THE SAFE ALLOWABLE FLOOR LOADS ON EACH FLOOR IN |
| POUNDS PER SQ FT. THE COMPUTATIONS & AFFIDAVIT SHALL BE |
| FILED AS A PERMANENT RECORD OF THE BLDG DEPT. |
| |
| 11) 110.4.3.SIGNS REQUIRED. IN EVERY BUILDING OR PART |
| OF A BUILDING USED FOR STORAGE, INDUSTRIAL OR HAZARDOUS |
| PURPOSES, THE SAFE FLOOR LOADS, AS REVIEWED BY THE |
| BUILDING OFFICIAL ON THE PLAN, SHALL BE MARKED ON |
| PLATES OF APPROVED DESIGN WHICH SHALL BE SUPPLIED & |
| SECURELY AFFIXED BY THE OWNER OF THE BUILDING IN A |
| CONSPICUOUS PLACE IN EACH STORY TO |
| WHICH THEY RELATE. SUCH PLATES SHALL NOT BE REMOVED OR |
| DEFACED, & IF LOST, REMOVED THE OWNER OF THE BUILDING |
| SHALL REPLACE THEM. PLEASE SEE FBC 1603.3 FOR MORE |
| INFORMATION. |
| |
| 12) DETAIL #3 FAILS TO INDICATE THE ATTACHMENT DETAIL |
| FOR THE FLOOR JOISTS. STATE THE TYPE OF CONNECTIONS FOR |
| THE FLOOR JOISTS TO THE LEDGER AND THE OUTER WALL. |
| INDICATE THE GRADE AND SPECIES OF THE FLOOR JOISTS ON |
| THE PLANS PER FBC 2308.8. THE PLANS FAIL TO SHOW |
| COLUMNS AND WALLS SUPPORTING THE MEZZANINE. THE |
| CONNECTION DETAIL FOR THE GUARDRAIL IS ALSO REQUIRED. |
| |
| 13) IS THE STAIRWAY BEING ENCLOSED? IF SO, THIS WILL |
| MAKE THE MEZZANINE AN ENCLOSED AREA. PLEASE SHOW |
| CLEARLY IF THE WALL AROUND THE STAIRS GOES TO THE DECK |
| ABOVE. |
| |
| MYRON JACOBS |
| BUILDING PLAN REVIEWER |
| (561)805-6726 |
| [email protected] |
| |
| |