2008-10-31 13:31:07PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET IR-1 INDICATES "IRRIGATION TAP AT DEDICATED 3"
 METER", HOWEVER THERE IS NO INDICATION OF BACKFLOW
 PROTECTION FOR THE POTABLE WATER. PER FBC-2004 PLUMBING
 SECTION 608.16.5 CONNECTIONS TO LAWN IRRIGATION
 SYSTEMS. THE POTABLE WATER SUPPLY TO LAWN IRRIGATION
 SYSTEMS SHALL BE PROTECTED AGAINST BACKFLOW BY AN
 ATMOSPHERIC-TYPE VACUUM BREAKER, A PRESSURE-TYPE VACUUM
 BREAKER OR A REDUCED PRESSURE PRINCIPLE BACKFLOW
 PREVENTER. A VALVE SHALL NOT BE INSTALLED DOWNSTREAM
 FROM AN ATMOSPHERIC VACUUM BREAKER. WHERE CHEMICALS ARE
 INTRODUCED INTO THE SYSTEM, THE POTABLE WATER SUPPLY
 SHALL BE PROTECTED AGAINST BACKFLOW BY A REDUCED
 PRESSURE PRINCIPLE BACKFLOW PREVENTER. CLEARLY INDICATE
 HOW THE POTABLE WATER WILL BE PROTECTED ON THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 *PLEASE CALL IF THERE ARE ANY QUESTIONS.
  