2008-11-04 09:10:44PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET A-1, DETAIL 2, DEMOLITION PLAN: IT APPEARS
 FROM THIS LAYOUT THAT THIS WAS AN R-2, OCCUPANCY AND
 FROM THE SUBMITTED PLANS THAT THIS OCCUPANCY IS BEING
 CHANGED TO A BUSSINESS. PLEASE CLARIFY AND CHANGE THE
 PERMIT APPLICATION. PER (W.P.B. AS AMENDED) SECTION 105
 PERMITS.
  
 2. SHEET A-1, A-2 FLOOR PLAN AND SHEET A-3 DETAIL 11,
 ROOM 218 IS A BATHROOM NOT AN EXISTING UTILITY ROOM.
 PLEASE CORRECT THIS ON THE RESUBMITTAL. PER (W.P.B. AS
 AMENDED) SECTION 106.1.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 3. DUE TO THE CHANGE OF OCCUPANCY THE FOLLOWING
 PLUMBING FIXTURES IN THE FOLLOWING ROOM NUMBERS NEED TO
 BE ACCESSIBLE PER THE FBC-2004 CHAPTER 11, FLORIDA
 ACCESSIBILITY CODE. ROOM 215, WATER CLOSET, LAVATORY
 AND BATHTUB. ROOM 217, SINK. ROOM 218, WATER CLOSET AND
 LAVATORY.
  
 *THE FOLLOWING ARE THE CODE SECTIONS FOR SAID
 ACCESSIBLE PLUMBING FIXTURES.
  
 **11-4.16 WATER CLOSETS (ELEVATION DETAIL REQUIRED WITH
 THE FOLLOWING INFORMATION)
 11-4.16.2 CLEAR FLOOR SPACE. SEE FIGURE 28.
 11-4.16.3 HEIGHT. 17" TO 19".
 11-4.16.4 GRAB BARS. SEE FIGURE 29. GRAB BAR BEHIND W/C
 36" LONG.
 11-4.16.5 FLUSH CONTROLS. MOUNTED ON WIDE SIDE MAX. 44"
 HIGH.
 11-4.16.6 DISPENSERS. SEE FIGURE 29(B).
  
 **11-4.19 LAVATORIES AND MIRRORS (ELEVATION DETAIL
 REQUIRED WITH THE FOLLOWING INFORMATION)
 11-4.19.2 HEIGHT AND CLEARANCES. MAXIMUM 34" TO RIM OR
 COUNTER. 29" A.F.F. TO THE BOTTOM OF THE APRON. (SEE
 FIGURE 31)
 11-4.19.3 CLEAR FLOOR SPACE.30" X 48" AND SHALL EXTEND
 A MAXIMUM OF 19" UNDERNEATH THE LAVATORY. (SEE FIGURE
 32)
 11-4.19.4 EXPOSED PIPES AND SURFACES. INSULATE TO
 PROTECT AGAINST CONTACT.
 11-4.19.5 FAUCETS. LEVER-OPERATED, PUSH-TYPE AND
 ELECTRONICALLY CONTROLLED ARE EXAMPLES.
 11-4.19.6 MIRRORS. 40" MAXIMUM A.F.F.
  
 ** 11-4.20 BATHTUBS (ELEVATION DETAIL REQUIRED WITH THE
 FOLLOWING INFORMATION)
 11-4.20.2 FLOOR SPACE. (SEE FIGURE 33)
 11-4.20.3 SEAT. REQUIRED. (SEE FIGURE 33 & 34)
 11-4.20.4 GRAB BARS. REQUIRED. (SEE FIGURE 33 & 34)
 11-4.20.5 CONTROLS. (SEE FIGURE 34)
 11-4.20.6 SHOWER UNIT. SHOWER SPRAY UNIT WITH A HOSE
 MINIMUM 60" LONG USED BOTH AS A FIXED OR HAND HELD
 SHALL BE PROVIDED.
  
 **11-4.24 SINKS (ELEVATION DETAIL REQUIRED WITH THE
 FOLLOWING INFORMATION)
 11-4.24.2 HEIGHT. MAXIMUM 34" A.F.F. TO RIM OR
 COUNTER.
 11-4.24.3 KNEE CLEARANCE. MINIMUM 27" HIGH, 30" WIDE,
 AND 19" DEEP.
 11-4.24.4 DEPTH. MAXIMUM 6-1/2" DEEP.
 11-4.24.5 CLEAR FLOOR SPACE. 30" X 48" AND CLEAR FLOOR
 SPACE SHALL EXTEND A MAXIMUM OF 19" UNDERNEATH THE SINK
 (NO CABINET DOORS, OPEN FRONT).
 11-4.24.6 EXPOSED PIPES AND SURFACES. INSULATE TO
 PROTECT AGAINST CONTACT.
 11-4.24.7 FAUCETS. LEVER-OPERATED, PUSH-TYPE, OR
 ELECTRONICALLY CONTROLLED ARE ACCEPTABLE DESIGNS.
 NOTE: SHEET A-3 DETAIL 2, KITCHEN 217, NEEDS TO BE
 REVISED ACCORDINGLY.
  
 11-4.22.2 DOOR. DOOR SWING NOT ALLOWED IN CLEAR FLOOR
 SPACE
 11-4.22.3 CLEAR FLOOR SPACE. WHEELCHAIR TURNING SPACE
 SHALL BE 180-DEGREE WITH A MINIMUM 60" CLEAR FLOOR
 SPACE (PER 11-4.2.3)
  
 4. SHEET A-1, OVERALL TENANT FLOOR PLAN DOES NOT
 INDICATE THE REQUIRED DRINKING FOUNTAIN FOR A BUSSINESS
 OCCUPANCY PER FBC-2004 PLUMBING TABLE 403.1 MINIMUM
 NUMBER OF REQUIRED PLUMBING FIXTURES. PLEASE KNOW THAT
 THE REQUIRED DRINKING FOUNTAIN SHALL BE ACCESSIBLE PER
 THE FOLLOWING FBC-2004 CHAPTER 11, FLORIDA
 ACCESSIBILITY CODE SECTIONS.
  
 **11-4.15 DRINKING FOUNTAINS (ELEVATION DETAIL REQUIRED
 WITH THE FOLLOWING INFORMATION)
 11-4.15.2 SPOUT HEIGHT. SPOUT HEIGHT 36" TO OUTLET
 MAXIMUM.
 11-4.15.3 SPOUT LOCATION. FRONT OF UNIT, WATER FLOW IN
 TRAJECTORY THAT IS PARALLEL OR NEARLY PARALLEL TO FRONT
 OF THE UNIT, WATER FLOW MINIMUM OF 4" HIGH. ON AN
 ACCESSIBLE OVAL OR ROUND BOWL FLOW OF WATER IS WITHIN
 3" OF THE FRONT OF FOUNTAIN.
 11-4.15.4 CONTROLS. SHALL BE FRONT MOUNTED OR SIDE
 MOUNTED NEAR FRONT EDGE.
 11-4.15.5 CLEARANCES. KNEE 27" HIGH, & 30" X 48" FLOOR
 SPACE.
 11-4.1.3(10)(A) WHERE ONLY ONE DRINKING FOUNTAIN IS
 PROVIDED ON A FLOOR, THERE SHALL BE A DRINKING FOUNTAIN
 WHICH IS ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS
 IN ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE
 TO THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.(THIS
 CAN BE ACCOMMODATED BY THE USE OF A HI-LO FOUNTAIN OR
 BY SUCH OTHER MEANS AS WOULD ACHIEVE THE REQUIRED
 ACCESSIBILITY FOR EACH GROUP ON EACH FLOOR).
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 *PLEASE CALL IF THERE ARE ANY QUESTIONS.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER