2008-10-29 11:10:13PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
  
 1) THE EX. UTILITY ROOM IS A BATHROOM, THE A.H.U. CAN
 NOT TAKE RETURN AIR FROM THE BATHROOM, THE LOUVERED
 DOOR TO THE A.H.U. CLOSET WILL PERMIT THIS TO HAPPEN.
 IF THE A.H.U. CLOSET IS TO BE AN OPEN PLENUM THAN A AIR
 TIGHT SEALED DOOR WILL NEED TO BE INSTALLED OR THE
 A.H.U. RETURN NEEDS TO BE DUCTED TO THE WALL GRILL. PER
 2004 FBC/M 403.2.1 (3) AND 407.1.
  
 2) THE EX. UTILITY ROOM (BATHROOM) REQUIRES AN EXHAUST
 FAN, PLEASE SHOW ON PLAN IF THEIR IS AN EXISTING FAN OR
 SHOW ONE TO BE INSTALLED, PER 2004 FBC/M TABLE 403.3.
  
 3) PLEASE SHOW ON PLAN HOW THE OUTDOOR AIR IS GETTING
 TO THE A.H.U., SEE 2004 FBC/M 401.2.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]