Plan Review Notes For Permit 08100508 |
Permit Number |
08100508 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-11-04 16:03:39 | *****DENIED***** | | | | | | 1. THE SUITE NUMBER SHALL BE INCLUDED IN THE ADDRESS | | LISTED IN THE TITLE BLOCK OF EACH SUBMITTED PLAN SHEET. | | | | 2. ON THE CVR SHEET UNDER LIFE SAFETY REQUIREMENTS, IT | | STATE THAT THERE ARE 3 EXITS PROVIDED BUT ONLY IS | | SHOWNIN THE PICTORIAL. WHERE ARE THE OTHER TWO? | | | | 3. SPECIFY THE INTERIOR FINISH MATERIALS FOR THE NEW | | WALL AND CEILING IN TERMS OF CLASS A, CLASS B, OR CLASS | | C. | | | | 4. SHOW THE LOCATION THE 2A:10BC RATED FIRE | | EXTINGUISHER(S) FOR THE NEW TENANT SPACE WITHIN THE 75 | | FEET TRAVEL DISTANCE. | | | | 5. PROVIDE A LAYOUT OF THE FIRE SPRINKLER HEADS FOR THE | | NEW TENANT SPACE. SPECIFICATIONS AND (OR) OTHER | | INFORMATION SHALL BE SUBMITTED UNER SEPARATE PLANS AND | | PERMIT. | | | | 6. PROVIDE A LAYOUT OF THE FIRE ALARM DEVICES FOR THE | | NEW TENANT SPACE. SPECIFICATIONS AND (OR) OTHER | | INFORMATION SHALL BE SUBMITTED UNER SEPARATE PLANS AND | | PERMIT. | | | | 7. WHERE IS THE EXIT AS INDICATED BY THE MEANS OF | | EGRESS TRAVEL (EAST) AS SHOWN IN THE CORRIDOR ON SHEET | | E2.1 - LIGHTING PLAN. | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING WHERE/HOW THE COMMENT WAS ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW |
|