2008-10-24 16:04:15 | RESIDENTIAL (R3) WINDOWS/DOOR BUILDING REVIEW |
| CHECKLIST. |
| REVIEW UNDER 2004 EXISTING BUILDING CODE WITH 2007 |
| REVISIONS. |
| |
| 1- REPLACEMENT OF WINDOWS AND DOORS WITH GLAZING ARE |
| REQUIRED TO HAVE IMPACT PROTECTION AS REQUIRED BY SEC. |
| 507.3 EXCEPTION ONE OF 2004 EXISTING BUILDING CODE. |
| PROVIDE PRODUCT APPROVAL FOR DOORS AND WINDOWS WITH |
| LARGE MISSILE IMPACT PROTECTION OR PROVIDE PRODUCT |
| APPROVAL FOR ANY TYPE OF SHUTTERS. |
| |
| 2- IS USING SHUTTERS PROVIDE COMPLETE INSTALLATION |
| SCHEDULE AS REQUIRED BY CITY IMPLEMENTATION STANDARD |
| FOR WIND-BORNE DEBRIS IMPACT PROTECTION. SEE ATTACHED |
| SAMPLE. COMPLETE THE INSTALLATION SCHEDULE AND MARK ON |
| DRAWINGS SPECIFIC SHUTTERS MOUNTING CONDITIONS AND |
| ANCHOR TYPE AND SPACING TO BE USED ACCORDING TO THE |
| DESIGN PRESSURES, EDGE DISTANCE, CONNECTION TYPE, PANEL |
| SPAN AND STRUCTURE TO BE ATTACHED TO (CONCRETE, |
| CONCRETE BLOCK OR WOOD). |
| |
| 3- SWINGING EXTERIOR DOOR PRODUCT APPROVAL SUBMITTED: |
| A) DRAWINGS AMW0015 SUBMITTED DON'T CORRESPOND TO |
| FLORIDA PRODUCT APPROVAL FL7945 SUBMITTED. GO TO |
| WWW.FLORIDABUILDING.ORG TO DOWNLOAD CORRESPONDING |
| DRAWINGS. |
| |
| B) THIS DOOR IS NOT APPROVED FOR USE WHERE LARGE |
| MISSILE IMPACT RESISTANCE IS REQUIRED. SEE NOTE #3 ON |
| SHEET 1 OF 5 OF DRAWINGS AMW0015. IF PROTECTING |
| OPENINGS WITH SHUTTERS, THEN COORDINATE WITH ITEM #1 |
| ABOVE. |
| |
| 4- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 |
| FLORIDA STATUTE. |
| |
| JULIO GOMEZ |
| BUILDING PLANS EXAMINER |