2008-10-24 16:04:15RESIDENTIAL (R3) WINDOWS/DOOR BUILDING REVIEW
 CHECKLIST.
 REVIEW UNDER 2004 EXISTING BUILDING CODE WITH 2007
 REVISIONS.
  
 1- REPLACEMENT OF WINDOWS AND DOORS WITH GLAZING ARE
 REQUIRED TO HAVE IMPACT PROTECTION AS REQUIRED BY SEC.
 507.3 EXCEPTION ONE OF 2004 EXISTING BUILDING CODE.
 PROVIDE PRODUCT APPROVAL FOR DOORS AND WINDOWS WITH
 LARGE MISSILE IMPACT PROTECTION OR PROVIDE PRODUCT
 APPROVAL FOR ANY TYPE OF SHUTTERS.
  
 2- IS USING SHUTTERS PROVIDE COMPLETE INSTALLATION
 SCHEDULE AS REQUIRED BY CITY IMPLEMENTATION STANDARD
 FOR WIND-BORNE DEBRIS IMPACT PROTECTION. SEE ATTACHED
 SAMPLE. COMPLETE THE INSTALLATION SCHEDULE AND MARK ON
 DRAWINGS SPECIFIC SHUTTERS MOUNTING CONDITIONS AND
 ANCHOR TYPE AND SPACING TO BE USED ACCORDING TO THE
 DESIGN PRESSURES, EDGE DISTANCE, CONNECTION TYPE, PANEL
 SPAN AND STRUCTURE TO BE ATTACHED TO (CONCRETE,
 CONCRETE BLOCK OR WOOD).
  
 3- SWINGING EXTERIOR DOOR PRODUCT APPROVAL SUBMITTED:
 A) DRAWINGS AMW0015 SUBMITTED DON'T CORRESPOND TO
 FLORIDA PRODUCT APPROVAL FL7945 SUBMITTED. GO TO
 WWW.FLORIDABUILDING.ORG TO DOWNLOAD CORRESPONDING
 DRAWINGS.
  
 B) THIS DOOR IS NOT APPROVED FOR USE WHERE LARGE
 MISSILE IMPACT RESISTANCE IS REQUIRED. SEE NOTE #3 ON
 SHEET 1 OF 5 OF DRAWINGS AMW0015. IF PROTECTING
 OPENINGS WITH SHUTTERS, THEN COORDINATE WITH ITEM #1
 ABOVE.
  
 4- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712