2009-02-09 17:11:08EXTERIOR STAIRWAY BUILDING REVIEW SECOND CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- CLARIFY WHICH BUILDING IS THE CONSTRUCTION TAKEN
 PLACE. PERMIT APPLICATION AND ARCHITECTURAL PLANS CALL
 FOR 1017 N. OLIVE AVE, WHILE NOTICE OF COMMENCEMENT
 CALLS FOR 1021 N. OLIVE AVE. ALSO, ACCORDING TO
 PROPERTY APPRAISAL WEBSITE PARCEL ID # SHOWN ON PERMIT
 APPLICATION CORRESPONDS TO 1021 N. OLIVE AVE. (REPEAT
 COMMENT).
 COORDINATE ALL INFORMATION AS REQUIRED, INCLUDING THE
 ARCHITECTURAL DRAWINGS TO HAVE CORRECT ADDRESS.
  
 2- PROVIDE NOTICE OF COMMENCEMENT WITH CORRECT ADDRESS
 AND PARCEL ID NUMBER. (REPEAT COMMENT).
 COORDINATE WITH ITEM #1 ABOVE.
 *** NOTE: NOTICE OF COMMENCEMENT NEEDS TO BE
 RE-RECORDED ALSO. IT EXPIRES AFTER 90 DAYS IF WORK IS
 NOT STARTED. IT WAS RECORDED ON 10/20/08.
 CORRECT NOTICE OF COMMENCEMENT MAY BE RECORDED AT TIME
 OF PERMIT PICK UP TO AVOID EXPIRATION OF IT.
  
 3- PROVIDE COMPLETE STAIRWAY FRAMING DETAILS AND
 SECTIONS TO VERIFY COMPLIANCE WITH TABLE 1607.1 FBC
 2004 AND SEC. 1609.1 FBC 2004 (NOTE: SPECIFY ALL LOADS
 TAKEN INTO CONSIDERATION FOR THE DESIGN). SHOW LOCATION
 OF STEEL COLUMNS AND WOOD COLUMNS. PROVIDE ANCHORING OF
 STAIRS AT BOTTOM (WRONG CONNECTOR. SEE ITEM #13 BELOW).
 SPECIFY STRINGERS AND CONNECTIONS (TOP & BOTTOM AT EACH
 LANDING). CLARIFY DETAIL CONNECTION AT TOP OF WOOD
 COLUMN (COORDINATE WITH DETAIL 3/SP). SPECIFY MATERIALS
 (TYPE OF WOOD AND GRADE) USED TO BUILD STAIRS. (REPEAT
 COMMENT). DETAILS PROVIDED ON SHEET A1 DON'T CORRESPOND
 TO FLOOR PLANS SHOWN ON SHEET SP. DESIGN LOADS FROM
 TABLE 1607.1 ARE NOT SPECIFIED.
  
 4- PROVIDE GUARDRAIL AND HANDRAIL DETAILS/SECTIONS TO
 SHOW COMPLIANCE WITH STRUCTURAL DESIGN TABLE 1607.1 AND
 SEC. 11-4.26.3 OF FBC 2004. (REPEAT COMMENT). DESIGN
 SPECIFICATIONS ARE NOT PROVIDED. AND, DETAILS DON'T
 SHOW HOW ARE THE PICKETS ATTACHED TO THE GUARDRAIL.
 ALSO, THERE ARE NOT DETAILS SHOWING ATTACHMENT OF
 HANDRAILS TO GUARDRAILS. SHOW HANDRAIL ON DETAIL 3/A1.
 ALSO, COORDINATE DETAIL 3/A1 WITH DETAIL A/SP (SEE BEAM
 CONNECTION).
  
 5- HANDRAILS NEED TO COMPLY WITH SEC. 11-4.9.4(2) AND
 FIGURE 19 OF CHAPTER 11 FBC 2004.
 ***NOTE: CHECK TOP AND BOTTOM HANDRAIL ENDING. (REPEAT
 COMMENT). HANDRAIL DOENS'T COMPLY AT TOP AND BOTTOM.
 ALSO, FLOOR PLANS ON SHEET SP DON'T SHOW THE HANDRAIL
 EXTENSIONS AT TOP AND BOTTOM.
  
 6- TYPICAL STAIR DETAILS ON SHEET A1 DON'T APPLY TO
 THIS PROJECT. THEY ARE FOR STAIRS ATTACHED TO A WALL.
 SEE PLANS AND REVISE AS REQUIRED. ALSO, REVISE SIZE OF
 HANDRAIL TO COMPLY WITH SEC. 11-4.26.2 FBC 2004.
 (REPEAT COMMENT).
  
 7- PROVIDE DETAILS SHOWING COMPLIANCE WITH THE
 GUARDRAIL OPENINGS LIMITATIONS, SEC 1012.3 FBC 2004.
 (REPEAT COMMENT). OPENING NOT TO ALLOW 4" SPHERE TO
 PASS THRU. NO 4" MAXIMUM. REVISE AS REQUIRED.
  
 8- PROVIDE PLANS SHOWING EXISTING STAIRS AND LANDINGS
 TO BE REMOVED. ACCORDING TO PICTURE PROVIDED IT LOOKS
 LIKE THE SWING OF THE DOOR IS GOING TO INTERFERE WITH
 THE EGRESS SINCE PROPOSED STAIRS ARE ORIENTED ON THE
 OTHER WAY SO THE SWING OF THE DOOR WILL BE IN THE
 EGRESS DIRECTION. CLARIFY HOW DEALING WITH THIS ISSUE.
 IF NEW DOOR WILL BE INSTALLED, THEN ADD TO THE SCOPE OF
 WORK AND PROVIDE PRODUCT APPROVAL FOR THE DOOR.
  
 9- OWES $80.80 FOR UPDATED VALUATION.
  
 10- SPECIFY TYPE OF ALTERATION AS REQUIRED BY SEC.
 301.5 OF 2004 FLORIDA EXISTING BUILDING CODE. (REPEAT
 COMMENT). THIS IS NOT LEVEL 1. REVIEW SEC. 301.5 AND
 REVISE AS REQUIRED. CHANGING CONFIGURATION OF STAIRS.
  
 11- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED
 BY DCA RULE 9B-72 FOR ALL SIMPSON STRUCTURAL CONNECTORS
 SPECIFIED ON PLANS.
 NOTE: PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL COVER
 PAGE AND PAGE WHERE CONNECTOR IS SHOWN. NO NEED TO
 PROVIDE COMPLETE REPORT. (REPEAT COMMENT). MISSING
 PRODUCT APPROVAL FOR CONNECTOR #4 SIMPSON TA10 SHOWN ON
 CONNECTOR SCHEDULE.
  
 12- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
 (REPEAT COMMENT). INFORMATION SUBMITTED SAYS "REVIEWED
 AND APPROVED" AND THEN THE DATE. BUT IT DOESN'T
 IDENTIFY THE DESIGNER OF RECORD WHO REVIEWED IT.
 ANYBODY CAN WRITE "REVIEWED AND APPROVED". CLARIFY
 REVIEWED AND APPROVED BY WHOM?. THE NAME OF THE
 DESIGNER OF RECORD IS NOT SHOWN. USE STANDARD SHOP
 DRAWINGS STAMP WITH COMPANY'S NAME OR WRITE IT DOWN ON.
 AND, SIGN IT RESPECTIVELY.
  
 13- DETAIL A/A1: CONNECTOR "TA10" SPECIFIED AT THE
 BOTTOM OF STAIRS DOESN'T WORK. THIS IS A CONNECTOR
 DESIGNED TO SUPPORT THE STAIR TREADS NOT THE WHOLE
 STAIR ASSEMBLY. SEE SIMPSON CATALOG AND REVISE AS
 REQUIRED.
  
 14- DETAIL 1/SP: CLARIFY WHAT'S THE DOUBLE LINE SHOWN
 IN THE MIDDLE OF STAIRS FROM INTERMEDIATE STAIR LANDING
 TO UPPER STAIR LANDING FOR?. SEE COMMENTS ON PLANS AND
 REVISE AS REQUIRED.
  
 ***NOTE: ONE SET OF PLANS WILL BE RETAINED IN THIS
 OFFICE TO VERIFY CHANGES AT TIME OF RE-SUBMITTAL.
 ARCHITECT TO REVIEW ATTACHED COPY OF FLORIDA STATUTE
 SEC. 553.80(2)(B) REGARDING DESIGN PROFESSIONALS AND
 MULTIPLE REVIEWS.
  