2008-11-12 16:32:39 | EXTERIOR STAIRWAY BUILDING REVIEW CHECKLIST. |
| REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. |
| |
| 1- CLARIFY WHICH BUILDING IS THE CONSTRUCTION TAKEN |
| PLACE. PERMIT APPLICATION AND ARCHITECTURAL PLANS CALL |
| FOR 1017 N. OLIVE AVE, WHILE NOTICE OF COMMENCEMENT |
| CALLS FOR 1021 N. OLIVE AVE. ALSO, ACCORDING TO |
| PROPERTY APPRAISAL WEBSITE PARCEL ID # SHOWN ON PERMIT |
| APPLICATION CORRESPONDS TO 1021 N. OLIVE AVE. |
| |
| 2- PROVIDE NOTICE OF COMMENCEMENT WITH CORRECT ADDRESS |
| AND PARCEL ID NUMBER. |
| |
| 3- PROVIDE COMPLETE STAIRWAY FRAMING DETAILS DETAILS |
| AND SECTIONS TO VERIFY COMPLIANCE WITH TABLE 1607.1 FBC |
| 2004 AND SEC. 1609.1 FBC 2004 (NOTE: SPECIFY ALL LOADS |
| TAKEN INTO CONSIDERATION FOR THE DESIGN). SHOW LOCATION |
| OF STEEL COLUMNS AND WOOD COLUMNS. PROVIDE ANCHORING OF |
| STAIRS AT BOTTOM. SPECIFY STRINGERS AND CONNECTIONS. |
| SPECIFY ATTACHMENT OF TOP STAIR LANDING TO EXISTING |
| BUILDING. PROVIDE COMPLETE DETAILS AND SIZE OF STEEL |
| BUCKET TO FASTEN TO STEEL COLUMN. CLARIFY DETAIL |
| CONNECTION AT TOP OF WOOD COLUMN. SPECIFY MATERIALS |
| USED TO BUILD STAIRS. |
| |
| 4- PROVIDE GUARDRAIL AND HANDRAIL DETAILS/SECTIONS TO |
| SHOW COMPLIANCE WITH STRUCTURAL DESIGN TABLE 1607.1 AND |
| SEC. 11-4.26.3 OF FBC 2004. |
| |
| 5- PROVIDE RISER, TREAD AND NOSING DETAILS TO VERIFY |
| COMPLIANCE WITH SEC. 11-4.9.2 AND 11-4.9.3 FBC 2004. |
| ***NOTE: OPEN RISERS ARE NOT ALLOWED. |
| |
| 6- HANDRAILS NEED TO COMPLY WITH SEC. 11-4.9.4(2) AND |
| FIGURE 19 OF CHAPTER 11 FBC 2004. |
| ***NOTE: CHECK TOP AND BOTTOM HANDRAIL ENDING. |
| |
| 7- TYPICAL STAIR DETAILS DON'T APPLY TO THIS PROJECT. |
| THEY ARE FOR STAIRS ATTACHED TO A WALL. REVISE SIZE OF |
| HANDRAIL TO COMPLY WITH SEC. 11-4.26.2 FBC 2004. CHECK |
| RISER AND TREAD SIZES. REVISE AS REQUIRED TO MATCH |
| PROPOSED STAIRS. |
| |
| 8- PROVIDE DETAILS SHOWING COMPLIANCE WITH THE |
| GUARDRAIL HEIGHT ( 42" AS REQUIRED BY SEC. 1012.2 FBC |
| 2004) , AND OPENINGS LIMITATIONS, SEC 1012.3 FBC 2004. |
| |
| 9- PROVIDE DETAILS SPECS SHOWING COMPLIANCE WITH |
| HANDRAIL HEIGHT AND OTHER REQUIREMENTS OF SEC. 11-4.9.4 |
| FBC 2004. |
| |
| 10- PLANS NEED TO SPECIFY SPECIFIC CODES AND YEAR (SEC. |
| 105.3 AND 105.3.1 OF CITY AMENDMENTS TO FBC 2004) AND |
| ALL INFORMATION REQUIRED BY SEC. 1603 FBC 2004. |
| NOTE: CITY OF WEST PALM BEACH IS LOCATED ON BASIC WIND |
| SPEED OF 140MPH. SEC. 117 CITY AMENDMENTS TO FBC 2004. |
| |
| 11- PROVIDE PLANS SHOWING EXISTING STAIRS AND LANDINGS |
| TO BE REMOVED. CLARIFY WHY EXISTING LANDING TO BE |
| REMOVED IS SHOWN LARGER THAN THE PROPOSED ONE. PROVIDE |
| INFORMATION SHOWING BUILDING USE AND NUMBER OF PEOPLE |
| TO VERIFY COMPLIANCE WITH MINIMUM REQUIRED WIDTH OF |
| MEANS OF EGRESS OF SEC. 1009.1 FBC 2004. (44" MINIMUM |
| UNLESS EXCEPTIONS APPLY). |
| |
| 12- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| LOW. UPDATE PERMIT VALUATION TO INCLUDE EXISTING STAIRS |
| DEMOLITION AND DEBRIS REMOVAL, PROFESSIONAL DESIGNER |
| FEES AND CONTRACTOR OVERHEAD AND PROFIT AS REQUIRED BY |
| SEC. 108.3 CITY AMENDMENTS TO FBC 2004. |
| |
| 13- SPECIFY TYPE OF ALTERATION AS REQUIRED BY SEC. |
| 301.5 OF 2004 FLORIDA EXISTING BUILDING CODE. |
| |
| 14- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE |
| 9B-72 FOR ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED |
| ON PLANS. |
| NOTE: PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL COVER |
| PAGE AND PAGE WHERE CONNECTOR IS SHOWN. NO NEED TO |
| PROVIDE COMPLETE REPORT. |
| |
| 15- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| |
| 16- SCALE FOR DRAWING DETAIL 4/SP IS INCORRECT. REVISE |
| AS REQUIRED. |
| |
| JULIO GOMEZ |
| BUILDING PLANS EXAMINER |
| (561)805-6712 |