Date |
Text |
2008-10-30 13:28:41 | PLUMBING PLAN REVIEW: |
| DENIED: |
| |
| PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| |
| 1. CLEARLY INDICATE THE CODE CYCLE ON THE PLANS. PER |
| CITY OF WPB AMENDMENTS TO CHAPTER 1, SECTION 106.1.1 |
| INFORMATION ON CONSTRUCTION DOCUMENTS AND SECTION 106.5 |
| RECORD RETENTION. |
| THE CURRENT CODE CYCLE FOR THE PLANS IS "FBC-2004 WITH |
| 2007 REVISIONS". |
| |
| 2. DECLARE THE LEVEL OF ALTERATION. PER FBC-2004 |
| EXISTING BUILDING CHAPTER 3. |
| |
| 3. THE ADDRESS IS INCOMPLETE ON ALL PLAN SHEETS. THE |
| SUITE NUMBER 110 IS MISSING FROM THE ADDRESS. PLEASE |
| CORRECT PER FBC-2004 CHAPTER 1, (W.P.B. AS AMENDED |
| SECTION 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS |
| AND SECTION 106.5 RECORD RETENTION. |
| |
| 4. SHEET A2 INTERIOR ELEVATION DETAIL (9) @ LOUNGE: |
| PLEASE CORRECT/ADD THE FOLLOWING REQUIRED INFORMATION |
| PER THE FBC-2004 CHAPTER 11, FLORIDA ACCESSIBILITY CODE |
| SECTION TO THE DETAIL FOR THE ACCESSIBLE SINK. |
| |
| *SECTION 11-4.24.2 HEIGHT. MAXIMUM 34" A.F.F. TO RIM OR |
| COUNTER. (DETAIL INCORRECTLY INDICATES 3'-0") |
| |
| *SECTION 11-4.24.3 KNEE CLEARANCE. MINIMUM 27" HIGH, |
| 30" WIDE, AND 19" DEEP. (OPEN FRONT REQUIRED, REMOVE |
| CABINET DOORS @ SINK) |
| |
| *SECTION 11-4.24.4 DEPTH. MAXIMUM 6-1/2" DEEP. |
| |
| 5. SHEET A4 DETAILS: PLEASE ADD THE FOLLOWING REQUIRED |
| INFORMATION PER THE FBC-2004 CHAPTER 11, FLORIDA |
| ACCESSIBILITY CODE SECTIONS FOR THE FOLLOWING |
| ACCESSIBLE PLUMBING FIXTURES. |
| |
| *DRINKING FOUNTAIN SECTION 11-4.15. |
| |
| SECTION 11-4.15.4 CONTROLS. SHALL BE FRONT MOUNTED OR |
| SIDE MOUNTED NEAR FRONT EDGE. |
| |
| SECTION 11-4.15.5 CLEARANCES. KNEE 27" HIGH. |
| |
| *WATER CLOSET SECTION 11-4.16. |
| |
| SECTION 11-4.16.5 FLUSH CONTROLS. MOUNTED ON WIDE SIDE |
| MAX. 44" HIGH. |
| |
| 6. SHEET P-1 DETAIL (2) SANITARY PLUMBING ISOMETRIC |
| DIAGRAM: PLEASE CORRECT THE FOLLOWING PER THE FBC-2004 |
| PLUMBING CODE SECTIONS. |
| |
| A} W.C. #2 DOES NOT REFLECT THE FLOOR PLAN OF SHEET A1. |
| PLEASE KNOW THAT THERE ARE TWO LAVATORIES BEING |
| INDICATED IN THE ISOMETRIC, HOWEVER THE FLOOR PLAN IS |
| ONLY INDICATING ONE LAVATORY. PLEASE CORRECT PER |
| SECTION 401.1 AND 701.1 SCOPE. |
| |
| B} EXAM ROOM #4 AND #5 CLEARLY INDICATE THE FIXTURE |
| TYPE ON THE ISOMETRIC. PER SECTION 401.1 AND 701.1 |
| SCOPE. |
| |
| C} PLEASE KNOW THAT THE LABORATORY SINK PLUMBING ON |
| BOTH THE SANITARY PLUMBING PLAN AND THE SANITARY |
| PLUMBING ISOMETRIC DIAGRAM IS BEING INDICATED IN THE |
| WRONG LOCATION AND DOES NOT REFLECT THE FLOOR PLAN OF |
| SHEET A1. PLEASE CORRECT PER SECTION 701.1 SCOPE. |
| |
| 7. SHEET P-2 DETAIL (2) WATER PLUMBING ISOMETRIC |
| DIAGRAM: PLEASE CLEARLY INDICATE THE REQUIRED FULL-OPEN |
| VALVE LOCATED ON THE WATER SUPPLY PIPE TO THE WATER |
| HEATER. PER FBC-2004 PLUMBING SECTION 606.1 LOCATION OF |
| FULL-OPEN VALVES (7). |
| |
| 8. THE WATER HEATER AND HOT WATER PIPE INSULATION ARE |
| MISSING FROM THE ENERGY CALCULATIONS. PER FBC-2004 |
| CHAPTER 13, TABLE 13-411.1.ABC.2 MINIMUM PIPE |
| INSULATION AND TABLE 13-412.1.ABC.3 PERFORMANCE |
| REQUIREMENTS FOR WATER HEATING EQUIPMENT. |
| |
| ********IMPORTANT INFORMATION******** |
| WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| END OF COMMENTS: |
| |
| *PLEASE CALL IF THERE ARE ANY QUESTIONS. |
| |
| REVIEW BY: MIKE PERSON |
| PLUMBING PLANS EXAMINER |
| PHONE= (561) 805-6730 |
| FAX= (561) 805-6731 |
| E-MAIL= [email protected] |