2008-10-28 08:27:41 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | (F.S.). | | | | *** DENIED *** | | | | 1) PLAN A3 SHOWS BATT INSULATION LYING ON THE | | ACOUSTICAL CEILING, PER 2004 FBC 13-404.1.ABC.1 ROOF | | INSULATION SHALL NOT BE INSTALLED ON A SUSPENDED | | CEILING WITH REMOVABLE CEILING PANELS. PLEASE CORRECT. | | | | 2) PLEASE SUBMIT A COPY OF THE ASHRAE 62 (2004 OR 2007) | | SECTION THAT DEMONSTRATES THE EQUATION USED FOR THE | | OUTDOOR AIR CALCULATIONS FOR THE WAITING ROOM. SEE 2004 | | FBC/M 403.4 AND ASHRAE 62.1-2004 SECTION 6.2.6.2. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|