Plan Review Notes
Plan Review Notes For Permit 08100423
Permit Number 08100423
Review Stop M
Sequence Number 1
Notes
Date Text
2008-10-28 08:27:41PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
  
 1) PLAN A3 SHOWS BATT INSULATION LYING ON THE
 ACOUSTICAL CEILING, PER 2004 FBC 13-404.1.ABC.1 ROOF
 INSULATION SHALL NOT BE INSTALLED ON A SUSPENDED
 CEILING WITH REMOVABLE CEILING PANELS. PLEASE CORRECT.
  
 2) PLEASE SUBMIT A COPY OF THE ASHRAE 62 (2004 OR 2007)
 SECTION THAT DEMONSTRATES THE EQUATION USED FOR THE
 OUTDOOR AIR CALCULATIONS FOR THE WAITING ROOM. SEE 2004
 FBC/M 403.4 AND ASHRAE 62.1-2004 SECTION 6.2.6.2.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]