Plan Review Notes For Permit 08100423 |
Permit Number |
08100423 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-10-31 10:04:02 | ***DENIED*** | | | | 1) IN ADDITION TO APPLICABLE BUILDING CODES, LIFE | | SAFETY SHALL COMPLY WITH NFPA 101, 2003. | | | | 2) MINIMUM 2A-10B,C RATED FIRE EXTINGUISHERS TO BE | | MOUNTED AT LOCATIONS NOT TO EXCEED 75' TRAVEL DISTANCE. | | | | 3) PROVIDE MINIMUM INTERIOR FINISH CLASSIFICATION FOR | | WALLS AND CEILING. | | | | 4) SHEET E-2 INDICATES A FIRE ALARM SYSTEM TO INCLUDE A | | CONTROL PANEL. IF FIRE ALARM SUPERVISES AN AUTOMATIC | | FIRE SPRINKLER SYSTEM, IT SHALL BE UL CERTFICATED PRIOR | | TO FINAL INSPECTION. | | | | 5) PLEASE INDICATE THE MAXIMUM TRAVEL DISTANCE ON THE | | SAFETY FLOOR PLAN. | | | | 6) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY | | WITH NFPA 241. | | | | | | MIKE WENNERGREN, ASST. FIRE MARSHAL | | FIRE PLAN REVIEW | | FIRE PREVENTION (561) 804-4756 |
|