2008-10-29 14:49:17 | |
| |
| |
| |
| APPLICATION #08100423 ELECTRICAL PLAN REVIEW |
| 3109 45TH STREET 10/28/08 |
| WEST PALM BEACH, FL. |
| |
| |
| |
| THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| |
| THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 |
| NEC, NFPA-72 2002, 2004 FBC AS AMENDED, CHAPTER 1, AND |
| FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| |
| 1} THIS PROJECT MUST COMPLY WITH CHAPTER 13 FBC. SEE |
| 13-415.1ABC.1.1 FOR AUTOMATIC CONTROL REQUIREMENTS AND |
| FOR LIGHTING DENSITIES. ALL THAT IS REQUIRED FOR THE |
| ELECTRICAL REVIEW IS THE BASIC PRESCRIPTIVE |
| REQUIREMENTS. SEE 13-415.2.ABC.1 PERFORMANCE |
| CALCULATION PROCEDURES, GENERAL. |
| THE INTERIOR LIGHTING POWER ALLOWANCE FOR A BUILDING OR |
| A SEPARATELY METERED OR PERMITTED PORTION OF A BUILDING |
| SHALL BE DETERMINED BY EITHER THE BUILDING AREA METHOD |
| DESCRIBED IN SECTION 415.2.C.1 OR THE SPACE-BY-SPACE |
| METHOD DESCRIBED IN SECTION 415.2.B.1. THE INSTALLED |
| INTERIOR LIGHTING POWER IDENTIFIED IN ACCORDANCE WITH |
| SECTION 415.2.ABC.1.1 SHALL NOT EXCEED THE INTERIOR |
| LIGHTING POWER ALLOWANCE DEVELOPED IN ACCORDANCE WITH |
| SECTION 415.2.C.1 OR 415.2.B.1. THIS CAN BE |
| DEMONSTRATED ON THE PLANS INDICATING THE WATTAGES OF |
| THE LUMINAIRES CHOSEN FOR THE PROJECT CONFORM TO THE |
| DENSITY REQUIREMENTS. INDICATE WATTAGES ON THE FIXTURE |
| SCHEDULE TO CORRELATE WITH THE ONES IN THE |
| CALCULATIONS. |
| |
| 2} INDICATE COMPLIANCE WITH 517.13 ON THE PLANS. THIS |
| CAN BE DONE IN NOTE FORM. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |
| BILL TROBAUGH |
| ELECTRICAL PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| 561/805-6718 |
| [email protected] |
| |
| |