2008-10-23 15:52:09 | 10-23-08 |
| BUILDING PLAN REVIEW |
| PERMIT: 08100423 |
| ADD: 3109 45TH STREET #100 |
| CONT: VILLA FRANCA DESIGN |
| TEL: (561)575-2288 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2007 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVIEW: 1ST |
| ACTION: DENIED |
| |
| 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| 2) NOTE: 713.13(6) THE POSTING OF THE NOTICE OF |
| COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST |
| INSPECTION. |
| |
| 3) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER |
| JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| BUILDING WITH THE 2007 SUPPLEMENTS. SHOW THIS |
| INFORMATION ON THE DRAWINGS. |
| |
| 4) 2004 FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN |
| OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF |
| ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF |
| THIS CODE. INDICATE THE LEVEL OF ALTERATION ON THE |
| PLANS. |
| |
| 5) SHEET A1 SHOWS TWO OPENINGS BEING CLOSED OFF AT |
| STORAGE ROOM #26 AND FUTURE EXAM ROOM #8: WILL THE |
| EXISTING DOOR REMAIN IN THE STORAGE ROOM? PROVIDE A |
| DETAIL DRAWING SHOWING WHAT MATERIAL WILL BE USED TO |
| CLOSE THE OPENINGS, HOW THE TOP AND BOTTOM SECTION OF |
| THE OPENINGS WILL BE ATTACHED TO THE EXISTING STRUCTURE |
| AND HOW THE RATING OF THE EXISTING WALLS WILL BE |
| MAINTAINED. A HEADER DETAIL IS REQUIRED FOR THE NEW |
| OPENING IN THE 18 INCH CONCRETE WALL. THE HEADER SHALL |
| CONSIST OF LINTEL OR SOME OTHER TYPE OF STRUCTURAL |
| CONSTRUCTION TO HOLD THE EXISTING CONCRETE IN PLACE. |
| FBC 2104.1.6 THE MINIMUM LENGTH OF END SUPPORT FOR |
| LINTELS SHALL BE 4 INCHES. ADDITIONAL INFORMATION IS |
| REQUIRED 106.1.2 |
| |
| 6) NOW THE SPACE IS ALTERED FIRE SPRINKLER PLANS ARE |
| REQUIRED TO SHOW THE NEW LAYOUT OF THE FIRE SPRINKLER |
| HEADS IN COMPARISON THE NEW ROOMS. THE NEW SPRINKLER |
| HEAD LOCATIONS MAY BE SHOWN ON THE CEILING PLANS ON |
| SHEET A3. FBC* 106.3.5.1.1(5) FS 553.79(2) |
| |
| 7) THE SOFFIT AND COVE LIGHT DETAILS ON SHEET A3 FAILS |
| TO INDICATE HOW THE TOP TRACK OR METAL STUDS WILL BE |
| ATTACHED TO THE STRUCTURE ABOVE AND WHAT TYPE OF |
| FASTENERS WILL BE USED. |
| |
| 8) SHEET A4; THE ROOM FINISH SCHEDULE FAILS TO SHOW THE |
| FINISHED OF THE WALLS. TABLE 803.5 MINIMUM INTERIOR |
| FINISH CLASSIFICATION; PROVIDE INFORMATION BASED ON |
| INTERIOR FINISH REQUIREMENTS BASED ON OCCUPANCY. PLEASE |
| INDICATE THE FLAME SPREAD PER THIS TABLE. |
| |
| 9) FBC 1210.2 WALLS WITHIN 2 FEET OF URINALS AND WATER |
| CLOSETS SHALL HAVE A SMOOTH, HARD, NONABSORBENT |
| SURFACE, T A HEIGHT OF 4 FEET. STATE THE WALL FINISHES |
| FOR THE BATHROOMS. |
| |
| MYRON JACOBS |
| BUILDING PLAN REVIEWER |
| (561)805-6726 |
| [email protected] |
| |