Date |
Text |
2008-10-24 16:49:39 | PLUMBING PLAN REVIEW: |
| DENIED: |
| |
| PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| |
| 1. PLEASE INCLUDE THE COMPLETE ADDRESS ON ALL PLAN |
| SHEETS INCLUDING THE SUITE NUMBER. PER FBC-2004 CHAPTER |
| 1, (W.P.B. AS AMENDED) SECTION 106.1.1 INFORMATION ON |
| CONSTRUCTION DOCUMENTS. |
| |
| 2. DECLARE THE GOVERNING CODE. (FBC-2004 WITH 2007 |
| REVISIONS) PER FBC-2004 CHAPTER 1, (W.P.B. AS AMENDED) |
| SECTION 106.5 RETENTION OF COSTRUCTION DOCUMENTS. |
| |
| 3. DECLARE THE LEVEL OF ALTERATION. PER FBC-2004 |
| EXISTING BUILDING CHAPTER 3. |
| |
| 4. PERMIT APPLICATION STATES "RELOCATE INTERIOR |
| BATHROOMS". PROVIDE AN EXISTING FLOOR PLAN LAYOUT |
| CLEARLY INDICATING THE LOCATION OF THE EXISTING |
| BATHROOMS BEFORE THEY WERE RELOCATED. PER FBC-2004 |
| CHAPTER 1, (W.P.B. AS AMENDED) SECTION 106.1.2 |
| ADDITIONAL DATA. ALSO INDICATE THE LOCATION OF THE |
| REQUIRED DRINKING FOUNTAIN ON THE EXISTING FLOOR PLAN |
| AND IF ONE IS NOT EXISTING PROVIDE ONE PER FBC-2004 |
| PLUMBING TABLE 403.1 MINIMUM NUMBER OF REQUIRED |
| PLUMBING FIXTURES FOR A BUSINESS OCCUPANCY 1 PER 100 IS |
| REQUIRED AND IT SHALL BE ACCESSIBLE PER THE FBC-2004 |
| CHAPTER 11, FLORIDA ACCESSIBILITY CODE SECTIONS. |
| |
| **11-4.15 DRINKING FOUNTAINS AND WATER COOLERS |
| (ELEVATION DETAIL REQUIRED WITH THE FOLLOWING |
| INFORMATION) |
| 11-4.15.2 SPOUT HEIGHT. SPOUT HEIGHT 36" TO OUTLET |
| MAXIMUM. |
| 11-4.15.3 SPOUT LOCATION. FRONT OF UNIT, WATER FLOW IN |
| TRAJECTORY THAT IS PARALLEL OR NEARLY PARALLEL TO FRONT |
| OF THE UNIT, WATER FLOW MINIMUM OF 4" HIGH. ON AN |
| ACCESSIBLE OVAL OR ROUND BOWL FLOW OF WATER IS WITHIN |
| 3" OF THE FRONT OF FOUNTAIN. |
| 11-4.15.4 CONTROLS. SHALL BE FRONT MOUNTED OR SIDE |
| MOUNTED NEAR FRONT EDGE. |
| 11-4.15.5 CLEARANCES. KNEE 27" HIGH, & 30" X 48" FLOOR |
| SPACE. |
| 11-4.1.3(10)(A) WHERE ONLY ONE DRINKING FOUNTAIN IS |
| PROVIDED ON A FLOOR, THERE SHALL BE A DRINKING FOUNTAIN |
| WHICH IS ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS |
| IN ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE |
| TO THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.(THIS |
| CAN BE ACCOMMODATED BY THE USE OF A HI-LO FOUNTAIN OR |
| BY SUCH OTHER MEANS AS WOULD ACHIEVE THE REQUIRED |
| ACCESSIBILITY FOR EACH GROUP ON EACH FLOOR). |
| |
| 5. SHEET A1 FLOOR PLAN: THE BATHROOM DOORS ARE SWINGING |
| OUT, HOWEVER ON SHEET M-P-1 DETAILS #1, 2, AND 3 THE |
| DOOR SWING IS BEING INDICATED AS IN. PLEASE KNOW THAT |
| PER FBC-2004 CHAPTER 11, FLORIDA ACCESSIBILITY CODE |
| SECTION 11-4.22.2 DOORS (1) DOORS SHALL NOT SWING INTO |
| THE CLEAR FLOOR SPACE OF ANY FIXTURE. PLEASE CORRELATE |
| RESUBMITTED PLAN SHEETS TO CLEARLY INDICATE AN OUTWARD |
| DOOR SWING. |
| |
| 6. SHEET A-1 CLEARLY INDICATE THE CLEAR FLOOR SPACE FOR |
| THE FOLLOWING FIXTURES COMPLIANT WITH THE FOLLOWING |
| FBC-2004 CHAPTER CODE SECTIONS. *WATER CLOSET SECTION |
| 11-4.16.2 SEE FIGURE 28 AND *LAVATORY SECTION 11-4.19.3 |
| CLEAR FLOOR SPACE.30" X 48" AND SHALL EXTEND A MAXIMUM |
| OF 19" UNDERNEATH THE LAVATORY. |
| |
| 7. SHEET A2 PLUMBING FIXTURE ELEVATION DETAIL FOR THE |
| WATER CLOSET: CLEARLY INDICATE THAT THE WATER CLOSET IS |
| COMPLIANT WITH THE FOLLOWING FBC-2004 CHAPTER 11, |
| FLORIDA ACCESSIBILITY CODE SECTION 11-4.16.5 FLUSH |
| CONTROLS. MOUNTED ON WIDE SIDE MAX. 44" HIGH. |
| |
| ********IMPORTANT INFORMATION******** |
| WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| END OF COMMENTS: |
| |
| *PLEASE CALL IF THERE ARE ANY QUESTIONS. |
| |
| REVIEW BY: MIKE PERSON |
| PLUMBING PLANS EXAMINER |
| PHONE= (561) 805-6730 |
| FAX= (561) 805-6731 |
| E-MAIL= [email protected] |