2008-10-23 10:14:59 | |
| 10-23-08 |
| BUILDING PLAN REVIEW |
| PERMIT: 08100422 |
| ADD: 3109 45TH STREET #100 |
| CONT: VILLA FRANCA DESIGN |
| TEL: (561)575-2288 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2007 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVIEW: 1ST |
| ACTION: DENIED |
| |
| 1) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| 2) NOTE: 713.13(6) THE POSTING OF THE NOTICE OF |
| COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST |
| INSPECTION. |
| |
| 3) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER |
| JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| BUILDING WITH THE 2007 SUPPLEMENTS. THIS INFORMATION |
| SHALL BE SHOWN ON THE PLANS. |
| |
| 4) (2004 FBC) 106.1.1 INFORMATION ON CONSTRUCTION |
| DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF |
| SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE & |
| EXTENT OF THE WORK PROPOSED & SHOW IN DETAIL THAT IT |
| WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| RELEVANT LAWS, ORDINANCES, AND RULES AND REGULATIONS AS |
| DETERMINED BY THE BUILDING OFFICIAL. SUBMIT AN EXISTING |
| FLOOR PLAN OF THE AREA PRIOR TO THE BATHROOM |
| INSTALLATION. |
| |
| 5) THE DESCRIPTION ON THE APPLICATION STATES ?RELOCATE |
| INTERIOR BATHROOMS? SHOW ON THE DRAWINGS WHERE THE |
| EXISTING BATHROOMS ARE AND WHERE THEY WILL BE RELOCATED |
| TO. |
| |
| 6) SHEET A1 SHOWS THE BATHROOM DOORS SWINGING OUT AND |
| SHEET M-P-1 SHOWS THEM SWINGING IN. THE FLOOR PLAN ON |
| EACH SHEET SHALL MATCH EACH OTHER. NOTE: FBC 11-4.22.2 |
| ALL DOORS TO ACCESSIBLE TOILET ROOMS SHALL COMPLY WITH |
| SECTION 11-4.13. DOORS SHALL NOT SWING INTO THE CLEAR |
| FLOOR SPACE REQUIRED FOR ANY FIXTURE. |
| |
| 7) THE FINISH SCHEDULE ON SHEET A1 FAILS TO INDICATE |
| THE WALL FINISHES IN THE BATHROOMS. NOTE: FBC 1202.2 |
| WALLS WITHIN 2 FEET OF URINALS AND WATER CLOSETS SHALL |
| HAVE A SMOOTH, HARD, NONABSORBENT SURFACE, TO A HEIGHT |
| OF 4 FEET ABOVE THE FLOOR. PLEASE PROVIDE ADDITIONAL |
| INFORMATION. |
| |
| 8) 2004 FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN |
| OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF |
| ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF |
| THIS CODE. INDICATE THE LEVEL ON THE DRAWINGS. |
| |
| MYRON JACOBS |
| BUILDING PLAN REVIEWER |