Plan Review Notes
Plan Review Notes For Permit 08100422
Permit Number 08100422
Review Stop B
Sequence Number 1
Notes
Date Text
2008-10-23 10:14:59 
 10-23-08
 BUILDING PLAN REVIEW
 PERMIT: 08100422
 ADD: 3109 45TH STREET #100
 CONT: VILLA FRANCA DESIGN
 TEL: (561)575-2288
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 2) NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 3) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS. THIS INFORMATION
 SHALL BE SHOWN ON THE PLANS.
  
 4) (2004 FBC) 106.1.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE &
 EXTENT OF THE WORK PROPOSED & SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, AND RULES AND REGULATIONS AS
 DETERMINED BY THE BUILDING OFFICIAL. SUBMIT AN EXISTING
 FLOOR PLAN OF THE AREA PRIOR TO THE BATHROOM
 INSTALLATION.
  
 5) THE DESCRIPTION ON THE APPLICATION STATES ?RELOCATE
 INTERIOR BATHROOMS? SHOW ON THE DRAWINGS WHERE THE
 EXISTING BATHROOMS ARE AND WHERE THEY WILL BE RELOCATED
 TO.
  
 6) SHEET A1 SHOWS THE BATHROOM DOORS SWINGING OUT AND
 SHEET M-P-1 SHOWS THEM SWINGING IN. THE FLOOR PLAN ON
 EACH SHEET SHALL MATCH EACH OTHER. NOTE: FBC 11-4.22.2
 ALL DOORS TO ACCESSIBLE TOILET ROOMS SHALL COMPLY WITH
 SECTION 11-4.13. DOORS SHALL NOT SWING INTO THE CLEAR
 FLOOR SPACE REQUIRED FOR ANY FIXTURE.
  
 7) THE FINISH SCHEDULE ON SHEET A1 FAILS TO INDICATE
 THE WALL FINISHES IN THE BATHROOMS. NOTE: FBC 1202.2
 WALLS WITHIN 2 FEET OF URINALS AND WATER CLOSETS SHALL
 HAVE A SMOOTH, HARD, NONABSORBENT SURFACE, TO A HEIGHT
 OF 4 FEET ABOVE THE FLOOR. PLEASE PROVIDE ADDITIONAL
 INFORMATION.
  
 8) 2004 FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN
 OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF
 THIS CODE. INDICATE THE LEVEL ON THE DRAWINGS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  
  
  
  
  
  