Notes
Date Text
2008-10-29 11:20:34***DENIED***
  
 1) LIFE SAFETY SHALL COMPLY WITH NFPA 101, 2003
 EDITION.
  
 2) PLEASE CORRELATE THE ADDRESS ON PLANS TO MATCH THE
 PERMIT APPLICATION.
  
 3) THE TERM SMOKE DETECTOR WOULD SUGGEST THAT THE
 DEVICES ARE TIED INTO THE BUILDING FIRE ALARM SYSTEM
 THAT WOULD INITIATE A GENERAL FIRE ALARM. DEVICES
 LOCATED IN THE LIVING UNITS THAT ARE RESPONSIVE TO
 SMOKE WOULD BE SMOKE ALARMS. PLEASE MAKE CORRECTION TO
 PLANS WHERE APPLICABLE.
  
 4) WILL WORK IMPACT THE FIRE SPRINKLER SYSTEM? SEPARATE
 SHOP DRAWINGS AND PERMITS MAY BE REQUIRED FOR FIRE
 SPRINKLER AND FIRE ALARM REMODEL.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756