Plan Review Notes
Plan Review Notes For Permit 08100386
Permit Number 08100386
Review Stop P
Sequence Number 1
Notes
Date Text
2009-02-17 17:42:24DENIED
 REFERENCE:
 FBC-2004 CHAPTER 1
  
 1. APPLICATION SHOWS A PLUMBING PERMIT NUMBER WAS
 APPLIED FOR. NO PLUMBING PLANS WERE SUBMITTED OR
 INDICATED. PLEASE INDICATE THE EXTENT OF THE PLUMBING
 PLANS ON THE FLOOR PLAN AND IF MOVING OR ADDING
 FIXTURES, THEN A SANITARY RISER DIAGRAM WILL BE
 REQUIRED SHOWING ALL PIPE SIZES, TRAPS & VENTS. IF
 REPLACING COMMON HOUSEHOLD PLUMBING FIXTURES TO
 EXISTING SUPPLY LINES AND OUTLETS, (NOT INCLUDING WATER
 HEATERS), THEN A PERMIT IS NOT REQUIRED. PLEASE
 CLARIFY. SECTIONS 105.2, 106.1.1 & 106.3.5.1.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved