| APPLICATION #08100386 ELECTRICAL PLAN REVIEW |
| 1025 UPLAND ROAD 2/9/09 |
| WEST PALM BEACH, FL. |
| |
| THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007 |
| REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND |
| FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| |
| 1} THERE IS NO SCALE FOR THE ELECTRICAL PLAN AND THE |
| ROOMS ARE NOT LABELED BUT IT APPEARS THE SPACING |
| REQUIREMENTS OF 210.52 ARE NOT BEING MET. CORRECT THE |
| ABOVE MENTIONED ISSUES. |
| |
| 2} THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL |
| COST OF LABOR AND MATERIAL. VALUATION REFERENCES MAY |
| INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL |
| CONSTRUCTION COST ANALYSIS SERVICES PER 108.3 FBC AS |
| AMENDED A PERMIT SHALL NOT BE ISSUED UNTIL FEES |
| AUTHORIZED UNDER SECTION 553.80, FLORIDA STATUTES, HAVE |
| BEEN PAID. 108.1 FBC. ADJUST THE VALUE AT THE PERMIT |
| CLERK???S DESK, AND PAY THE DIFFERENCE IN FEES PRIOR TO |
| RESUBMITTING. |
| |
| 3} INDICATE IF THE DEVICES ON THE PLAN ARE NEW OR |
| EXISTING. 106.1.1. |
| |
| 4} 408.4 CIRCUIT DIRECTORY OR CIRCUIT IDENTIFICATION, |
| PROVIDE A PANEL SCHEDULE WITH WIRE SIZES AND |
| OVERCURRENT PROTECTION RATINGS SO THAT COMPLIANCE WITH |
| 240 AND 310.16 MAY BE REVIEWED. |
| |
| 5} INDICATE THE RATING OF THE EXISTING SERVICE. 215.5 |
| NEC. |
| |
| 6} LOCATE THE PANEL ON THE PLAN. |
| |
| 7} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH |
| 210.52(A), 210.52(C), AND 210.8(A)(6) GFI. |
| |
| 8} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS. |
| WHEN INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS |
| REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING |
| ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE |
| INDIVIDUAL DWELLING UNIT SHALL BE PROVIDED WITH SMOKE |
| ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE |
| ALARMS SHALL BE INTERCONNECTED AND HARD WIRED. INDICATE |
| INTERCONNECTION AND LOCATE THE ALARMS ON THE PLAN. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |
| BILL TROBAUGH |
| ELECTRICAL PLANS EXAMINER |
| CITY OF WEST PALM BEACH |