Plan Review Notes For Permit 08100386 |
Permit Number |
08100386 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-02-13 13:45:33 | 2004 FBC W/2007 REVISIONS | | STRUCTURAL REPAIRS | | | | DENIED BY BUILDING | | | | 1) SUBMIT TWO SETS OF DRAFTSMAN QUALITY PLANS DRAWN TO | | A MINIMUM 1/8" SCALE THAT CLEARLY DESCRIBE THE LOCATION | | AND SCOPE OF WORK TO BE DONE. SPECIFY THE DIMENSIONS, | | SPANS, SPACING ETC. OF THE STRUCTURAL FRAMING. FBC | | 106.1.1* CITY AMENDMENTS | | | | 2) ON THE PLANS, SPECIFY THE CONNECTORS THAT WILL BE | | USED TO ATTACH THE FRAMING MEMBERS TO PROVIDE A | | CONTINUOUS LOAD PATH TO TRANSFER ALL LOADS TO THE | | FOUNDATION AS REQUIRED BY FBC R301.1. | | | | 3) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE | | CONNECTORS AS REQUIRED BY DCA RULE 9B-72. | | | | 4) SUBMIT TWO COPIES OF A FLOOR PLAN INDICATING THE | | AREAS WERE THE PROPOSED WORK WILL BE DONE. FBC 106.1.1* | | CITY AMENDMENTS | | | | 5) THE VALUE OF THE WORK ON THE APPLICATION APPEARS TO | | BE TOO LOW. THE VALUE IS TO INCLUDE THE COST OF LABOR, | | MATERIALS, OVERHEAD AND PROFIT AS WOULD BE CHARGED BY A | | CONTRACTOR. PLEASE ADJUST THE VALUE ACCORDINGLY. FBC | | 108.3 | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|