2010-01-15 14:20:38 
 ** DENIED 4TH REVIEW *
  
 ** SECOND REVIEW UNDER ACTUAL PERMIT APPLICATION. FIRST
 TWO REVIEWS WERE UNDER * PLAN REVIEW ONLY*.
  
 1) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR THE SAME CODE SECTIONS NOTED ON
 EACH REVIEWS. THIS IS THE SECOND REVIEW UNDER ACTUAL
 PERMIT APPLICATION, IF PLANS COME BACK IN FOR ONE MORE
 REVIEW WITH THE SAME CODE COMPLIANCE COMMENTS NOTED A
 4X FEE FOR THE PLAN REVIEW PORTION OF THE PERMIT FEE
 SHALL BE ASSESSED. THIS IS ONLY GIVEN AS A NOTICE AT
 THIS TIME.
  
 2) NOTE: IN AN EFFORT TO ALLEVIATE FURTHER REVIEWS AND
 REPEAT COMMENTS THIS REVIEWER CALLED FIRM LISTED ON
 TITLE BLOCKS REQUESTING TO SPEAK TO THE ENGINEER OF
 RECORD. THE STAFF INDIVIDUAL FIRST STATED NO SUCH
 PERSON WORKED FOR THEIR FIRM. AFTER SEVERAL QUESTIONS,
 STAFF THEN STATED THIS ENGINEER WAS ACTUALLY AN OUTSIDE
 CONSULTANT AND DID NOT WORK FOR INTERPLAN. THE CALL WAS
 NOT RECEIVED WELL AND STAFF DID NOT SEEM TO KEEP
 ATTENTION TO CALL. CALL WAS TERMINATED BY REVIEWER AS
 NO ACCOMPLISHMENT WAS BEING MADE.
 ENGINEER OF RECORD SHALL LIST HIS OR HER INFORMATION ON
 TITLE BLOCK IF THEY ARE NOT UNDER THE DIRECT EMPLOYMENT
 OF FIRM LISTED. PLEASE CONTACT BOARD OF ENGINEERS AND
 DEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION.
 THIS HAS BEEN CONFIRMED WITH FBPE.
 THE STATE HAD THE INFORMATION FOR ENGINEER OF RECORD IS
 WITH DESIGN PLUS INC. PLEASE PROVIDE CERTIFICATE OF
 AUTHORIZATION NUMBER AS LISTED WITH THE STATE OF
 FLORIDA.
  
 DESIGN PLUS INC
 664 OAK HOLLOW WAY
 ALTAMONTE SPRINGS, FL. 32714
 CA # 26340
 ** THIS INFORMATION IS REQUIRED ALSO ON MECHANICAL
 SHEETS.
 ** TO ALLEVIATE RE-PRINTING OF ALL SHEETS, THIS MAY BE
 ADDED BY A STAMP, TITLE BLOCK STICKER OR NEATLY
 HANDWRITTEN.
  
 PLEASE PROVIDE REVISED TITLE BLOCK FOR ENGINEER OF
 RECORD. PLEASE SEE FLORIDA ADMINISTRATIVE CODE
 61G15-23.002, FS 471.025, 471.023.
  
 3) NOTE: AS REQUESTED ON ALL PREVIOUS REVIEWS PLEASE BE
 SURE TO SEE FBC 13-415.AB.5, 13-415.AB.2.2 AND
 13-400.0.A, 13-101.1.1
 PLEASE BE SURE ALL SYSTEMS, COMPONENTS AND ITEMS ON
 PLANS WHICH AFFECT THE ENERGY CONSUMPTION AND
 EFFICIENCY OF THE BUILDING ARE PLACED INTO THE INPUT
 DATA REPORT OF THE SUBMITTED CALCULATIONS.
 A) ALL EXTERIOR LIGHTING IS REQUIRED TO BE PLACED INTO
 THE IDR. THIS WAS SPECIFICALLY MENTIONED ON THE
 PREVIOUS REVIEW YET THERE ARE SOME FIXTURES STILL NOT
 PART OF THE IDR. THE SAME FIXTURES WERE NOTED ABOVE A
 CALL WAS PLACED TO FIRM TO FIND OUT WHERE ALL OF THE
 1000W FIXTURES AND 400WATT FIXTURES ARE FED FROM. THESE
 ARE SHOWN ON SITE PHOTO-METRICS, HOWEVER NONE OF THESE
 FIXTURES ARE IN THE IDR.
 PLEASE E-0 INDICATES 3 MWD FIXTURES ON EXTERIOR WALLS
 HOWEVER LIGHTING PLANS ONLY INDICATE ONE OF THESE
 FIXTURES? THE ADDITIONAL FIXTURES ARE NOT IN THE IDR
 EITHER?
 CIRCUITING? CIRCUITING ON SCHEDULES?
 ONLY THE MINIMUM NEEDS TO BE SHOWN AT THIS TIME.
  
 4) NOTE: PREVIOUS NOTE WITH RESPECT TO 250.94 AND
 INTERSYSTEM BONDING WAS ADDRESSED BY A SPEC SHEET FOR
 SPECIFICATION BOOK. PLEASE PROVIDE ON PLANS.
 SPECIFICATION BOOKS ARE NOT USED FOR INSPECTIONS.
 IF THIS IS THE ONLY COMMENT WHICH NEEDS TO BE DONE,
 PLANS CAN BE REDLINED WITH THIS INFORMATION FROM
 REVIEWER AND REVISED AT A LATER DATE.
  
 5) NOTE: PREVIOUS NOTE WITH RESPECT TO 406.8 WAS NOT
 REVISED ON PLANS. RESPONSE MENTION NOTED ADDED TO SHEET
 E-4 HOWEVER NOTE COULD NOT BE FOUND. THIS CAN ALSO BE
 RED-LINED WITHOUT REVISING SHEET.
  
 6) NOTE: PREVIOUS NOTE #8, RESPONSE MENTIONS TO BE
 HARD-WIRED, HOWEVER PLEASE KNOW THIS STILL DOES NOT
 ALLOW THE USE OF CORDS.
 THIS CAN BE REDLINED ON PLANS. PLEASE BE SURE TO VERIFY
 LISTING OF EQUIPMENT SO THAT LISTING IS NOT VOIDED.
 400.8(2)
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved