2009-10-30 12:49:24REVIEW #: 1ST FOR PERMIT
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 PLANS HAVE BEEN STAMPED. HOWEVER, THE REVIEW WILL
 REMAIN IN FAIL STATUS PENDING SUBMISSION OF THE CORRECT
 ENERGY CODE COMPLIANCE FORM. THE FORM SUBMITTED, FORM
 400A-2004R, IS NO LONGER VALID AS OF MARCH 1, 2009.
 PLEASE SUBMIT A COMPLETED FORM 400A-08 WHICH MATCHES
 THE SUBMITTED PLANS AND COOLING LOAD CALCULATIONS. THE
 FOLLOWING PROVISO CONDITIONS ARE MARKED ON THE PLANS:
  
 **PROVISO**
  
 1. REVISE EQUIPMENT SCHEDULE TO SHOW HP-1 AND HP-2
 ASSOCIATED WITH AHU-1. THIS NUMBERING CONVENTION HAS
 HP-3 ASSOCIATED WITH AHU-2, ETC. PROPERLY IDENTIFY EACH
 PIECE OF EQUIPMENT AND THE AREA IT SERVES IN ACCORDANCE
 WITH FBC-M 304.11.
  
 2. PROVIDE MANUFACTURER'S WIND RESISTANCE DATA SHOWING
 ALL OUTDOOR APPLIANCES ARE DESIGNED FOR WIND RESISTANCE
 IN ACCORDANCE WITH FBC-M 301.12. IF SUCH DOCUMENTATION
 INCLUDES INSTALLATION INSTRUCTIONS, ADJUST DETAILS ON
 PLANS TO CORRESPOND WITH THE MANUFACTURER'S
 DOCUMENTATION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]