Plan Review Notes For Permit 08100349 |
Permit Number |
08100349 |
|
Review Stop |
M |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2009-10-30 12:49:24 | REVIEW #: 1ST FOR PERMIT | | ACTION: DENIED | | | | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | PLANS HAVE BEEN STAMPED. HOWEVER, THE REVIEW WILL | | REMAIN IN FAIL STATUS PENDING SUBMISSION OF THE CORRECT | | ENERGY CODE COMPLIANCE FORM. THE FORM SUBMITTED, FORM | | 400A-2004R, IS NO LONGER VALID AS OF MARCH 1, 2009. | | PLEASE SUBMIT A COMPLETED FORM 400A-08 WHICH MATCHES | | THE SUBMITTED PLANS AND COOLING LOAD CALCULATIONS. THE | | FOLLOWING PROVISO CONDITIONS ARE MARKED ON THE PLANS: | | | | **PROVISO** | | | | 1. REVISE EQUIPMENT SCHEDULE TO SHOW HP-1 AND HP-2 | | ASSOCIATED WITH AHU-1. THIS NUMBERING CONVENTION HAS | | HP-3 ASSOCIATED WITH AHU-2, ETC. PROPERLY IDENTIFY EACH | | PIECE OF EQUIPMENT AND THE AREA IT SERVES IN ACCORDANCE | | WITH FBC-M 304.11. | | | | 2. PROVIDE MANUFACTURER'S WIND RESISTANCE DATA SHOWING | | ALL OUTDOOR APPLIANCES ARE DESIGNED FOR WIND RESISTANCE | | IN ACCORDANCE WITH FBC-M 301.12. IF SUCH DOCUMENTATION | | INCLUDES INSTALLATION INSTRUCTIONS, ADJUST DETAILS ON | | PLANS TO CORRESPOND WITH THE MANUFACTURER'S | | DOCUMENTATION. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] |
|