2009-10-30 10:51:01 | ** DENIED ** |
| |
| 1) NOTE: AS NOTED ON PREVIOUS REVIEW PLANS HAD NOT BEEN |
| SUBMITTED FOR PERMIT THEREFORE ALL PLANS AND SUPPORTING |
| DOCUMENTS WOULD BE REQUIRED TO BE REVISED BASED ON THE |
| CODE AT THE TIME OF PERMIT APPLICATION. |
| THE RESPONSE MENTIONS PLANS WERE REVISED TO THE 2007 |
| FLORIDA BUILDING CODE HOWEVER SUBMITTED ENERGY |
| CALCULATIONS ARE FROM THE 2004 FLORIDA BUILDING CODE. |
| PLEASE ALSO KNOW THAT AS OF OCTOBER 1ST, 2009 THE |
| FLORIDA BUILDING CODE AND OTHER ADOPTED CODES HAVE ONCE |
| AGAIN CHANGED. THE SECOND SET OF 2009 SUPPLEMENTS OF |
| THE 2007 FBC HAVE BEEN IMPLEMENTED AND ADOPTED BY |
| STATUTES. |
| THIS INCLUDES THE ADOPTION OF THE 2008 NFPA-70. |
| ON THE PREVIOUS REVIEW NOTES WERE GIVEN FOR CODES. |
| THE PLANS STATE THE 2007 NFPA-101 HOWEVER PREVIOUS |
| REVIEW HAVE NOTE TO THE 2006 NFPA-101 AS ADOPTED ON |
| DECEMBER 31ST, 2008. THERE IS NO 2007 NFPA-101. |
| THE PLANS ALSO STATE THE 2007 NATIONAL ELECTRICAL CODE. |
| HOWEVER PREVIOUS NATIONAL ELECTRICAL CODE WAS THE 2005 |
| EDITION AND NOW THE 2008 EDITION HAS BEEN ADOPTED. |
| PLEASE BE SURE TO GO THROUGH THE 2008 NEC FOR NUMEROUS |
| CHANGES AND REVISE PLANS ACCORDINGLY. |
| |
| 2) NOTE: AS NOTED ON PREVIOUS REVIEW PLEASE COORDINATE |
| ALL ITEMS ON PLANS WITH THE SUBMITTED ENERGY |
| CALCULATIONS. |
| THE INPUT DATA REPORT AND PLANS DO NOT MATCH. 13-101.1, |
| 13-400.0.A,13-400.3.AB.3, 13-415.AB.5, 13-415.AB.2.2 |
| ETC |
| |
| EXAMPLE: THE IDR STILL DOES NOT INDICATE ALL EXTERIOR |
| LIGHTING LOCATED ON PLANS. IN FACT THE IDR ONLY |
| INDICATES A TOTAL OF THREE 100W LIGHT FIXTURES. THIS IS |
| NOT POSSIBLE WHEN SHEET E-2 CONTAINS MORE THAN 30 |
| FIXTURES. SHEET E2 CONTAINS NUMEROUS 1080W FIXTURES, |
| SEVERAL 455W MH FIXTURES, ETC. THE TOTAL NUMBER OF 100W |
| MLD FIXTURES IS 19. |
| THERE ARE OTHERS. |
| EXAMPLE: THE IDR INDICATES CARPET AND RUBBER PADDING |
| FOR ALL AREAS INCLUDING ZONE #4 WHICH CAN NOT CONTAIN |
| CARPET AND RUBBER PADDING. |
| |
| EXAMPLE: PLEASE SEE THE IDR WHICH INDICATES MANUAL ON/ |
| OFF CONTROLS WHICH IS NOT ACCURATE. |
| |
| EXAMPLE: PLEASE REVISE THE INTERIOR LIGHTING WHICH HAS |
| BEEN REVISED ON PLANS. |
| |
| 3) NOTE: NEW NOTE FOR 2008 NEC. PLEASE SEE 250.94 FOR |
| REQUIRED INTERSYSTEM BOND. |
| THE NEW SPECS BOOKS SUBMITTED CONTAIN A REFERENCE TO A |
| 250.94C, HOWEVER THIS IS FROM SEVERAL CODE CYCLES AGO |
| AS THERE IS NO CURRENT 250.94C. (1996 NEC). |
| PLEASE PROVIDE DETAILS FOR NEW REQUIRED BOND. |
| |
| 4) NOTE: PLEASE SEE 406.8 FOR REQUIRED RECEPTACLES |
| OUTSIDE IN DAMP OR WET LOCATIONS. |
| |
| 5) NOTE: PLEASE SEE FS 655.692. PLANS CONTAIN A NOTE #7 |
| ON SHEET E-2 WHICH STATE A 2 FOOT CANDLE MINIMUM IN THE |
| 5FT RADIUS FOR ATM. HOWEVER PER 655.962 (1)(A) REQUIRES |
| 10FT CANDLE. THE AREAS OUT FROM THERE INCLUDE 2 FT |
| CANDLE FOR 50FT AND PARKING REQUIREMENTS. |
| |
| 6) NOTE: ON PREVIOUS REVIEW IT WAS REQUESTED TO SUBMIT |
| THE MANUFACTURES SPECS/CUT SHEET FOR THE PROPOSED |
| TRANSFER SWITCH. THE RESPONSE MENTIONS IT WILL BE |
| LISTED HOWEVER NO SPECS OR SPECIFIC INFORMATION WAS |
| SUBMITTED. THERE ARE PRODUCTS AVAILABLE WHICH ARE NOT |
| 1008 LISTED OR MEET MINIMUM STANDARDS FOR TRANSFER OF |
| POWER. NEC 702.4,702.5 ( ALL) , 702.6, 90.7, 110.3 ETC |
| |
| 7) NOTE: PREVIOUS REVIEW NOTES WITH RESPECT TO MINIMUM |
| WIND LOADS TO BE ON PLANS PER 1609 OF THE FBC ARE NOT |
| DONE. RESPONSE MENTIONS NOTES ADDED TO PLANS HOWEVER NO |
| WIND LOAD INFORMATION IS ON SITE PLANS. |
| |
| 8) NOTE: PLANS INDICATE RECEPTACLES FOR DYE PACKS ABOVE |
| CEILING. HOWEVER PER 400.8(2) CORD AND PLUG CONNECTIONS |
| ABOVE CEILINGS ARE NOT PERMITTED. THIS INCLUDES CORDS |
| AS NOTED. |
| |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |