Plan Review Notes
Plan Review Notes For Permit 08100349
Permit Number 08100349
Review Stop E
Sequence Number 3
Notes
Date Text
2009-10-30 10:51:01** DENIED **
  
 1) NOTE: AS NOTED ON PREVIOUS REVIEW PLANS HAD NOT BEEN
 SUBMITTED FOR PERMIT THEREFORE ALL PLANS AND SUPPORTING
 DOCUMENTS WOULD BE REQUIRED TO BE REVISED BASED ON THE
 CODE AT THE TIME OF PERMIT APPLICATION.
 THE RESPONSE MENTIONS PLANS WERE REVISED TO THE 2007
 FLORIDA BUILDING CODE HOWEVER SUBMITTED ENERGY
 CALCULATIONS ARE FROM THE 2004 FLORIDA BUILDING CODE.
 PLEASE ALSO KNOW THAT AS OF OCTOBER 1ST, 2009 THE
 FLORIDA BUILDING CODE AND OTHER ADOPTED CODES HAVE ONCE
 AGAIN CHANGED. THE SECOND SET OF 2009 SUPPLEMENTS OF
 THE 2007 FBC HAVE BEEN IMPLEMENTED AND ADOPTED BY
 STATUTES.
 THIS INCLUDES THE ADOPTION OF THE 2008 NFPA-70.
 ON THE PREVIOUS REVIEW NOTES WERE GIVEN FOR CODES.
 THE PLANS STATE THE 2007 NFPA-101 HOWEVER PREVIOUS
 REVIEW HAVE NOTE TO THE 2006 NFPA-101 AS ADOPTED ON
 DECEMBER 31ST, 2008. THERE IS NO 2007 NFPA-101.
 THE PLANS ALSO STATE THE 2007 NATIONAL ELECTRICAL CODE.
 HOWEVER PREVIOUS NATIONAL ELECTRICAL CODE WAS THE 2005
 EDITION AND NOW THE 2008 EDITION HAS BEEN ADOPTED.
 PLEASE BE SURE TO GO THROUGH THE 2008 NEC FOR NUMEROUS
 CHANGES AND REVISE PLANS ACCORDINGLY.
  
 2) NOTE: AS NOTED ON PREVIOUS REVIEW PLEASE COORDINATE
 ALL ITEMS ON PLANS WITH THE SUBMITTED ENERGY
 CALCULATIONS.
 THE INPUT DATA REPORT AND PLANS DO NOT MATCH. 13-101.1,
 13-400.0.A,13-400.3.AB.3, 13-415.AB.5, 13-415.AB.2.2
 ETC
  
 EXAMPLE: THE IDR STILL DOES NOT INDICATE ALL EXTERIOR
 LIGHTING LOCATED ON PLANS. IN FACT THE IDR ONLY
 INDICATES A TOTAL OF THREE 100W LIGHT FIXTURES. THIS IS
 NOT POSSIBLE WHEN SHEET E-2 CONTAINS MORE THAN 30
 FIXTURES. SHEET E2 CONTAINS NUMEROUS 1080W FIXTURES,
 SEVERAL 455W MH FIXTURES, ETC. THE TOTAL NUMBER OF 100W
 MLD FIXTURES IS 19.
 THERE ARE OTHERS.
 EXAMPLE: THE IDR INDICATES CARPET AND RUBBER PADDING
 FOR ALL AREAS INCLUDING ZONE #4 WHICH CAN NOT CONTAIN
 CARPET AND RUBBER PADDING.
  
 EXAMPLE: PLEASE SEE THE IDR WHICH INDICATES MANUAL ON/
 OFF CONTROLS WHICH IS NOT ACCURATE.
  
 EXAMPLE: PLEASE REVISE THE INTERIOR LIGHTING WHICH HAS
 BEEN REVISED ON PLANS.
  
 3) NOTE: NEW NOTE FOR 2008 NEC. PLEASE SEE 250.94 FOR
 REQUIRED INTERSYSTEM BOND.
 THE NEW SPECS BOOKS SUBMITTED CONTAIN A REFERENCE TO A
 250.94C, HOWEVER THIS IS FROM SEVERAL CODE CYCLES AGO
 AS THERE IS NO CURRENT 250.94C. (1996 NEC).
 PLEASE PROVIDE DETAILS FOR NEW REQUIRED BOND.
  
 4) NOTE: PLEASE SEE 406.8 FOR REQUIRED RECEPTACLES
 OUTSIDE IN DAMP OR WET LOCATIONS.
  
 5) NOTE: PLEASE SEE FS 655.692. PLANS CONTAIN A NOTE #7
 ON SHEET E-2 WHICH STATE A 2 FOOT CANDLE MINIMUM IN THE
 5FT RADIUS FOR ATM. HOWEVER PER 655.962 (1)(A) REQUIRES
 10FT CANDLE. THE AREAS OUT FROM THERE INCLUDE 2 FT
 CANDLE FOR 50FT AND PARKING REQUIREMENTS.
  
 6) NOTE: ON PREVIOUS REVIEW IT WAS REQUESTED TO SUBMIT
 THE MANUFACTURES SPECS/CUT SHEET FOR THE PROPOSED
 TRANSFER SWITCH. THE RESPONSE MENTIONS IT WILL BE
 LISTED HOWEVER NO SPECS OR SPECIFIC INFORMATION WAS
 SUBMITTED. THERE ARE PRODUCTS AVAILABLE WHICH ARE NOT
 1008 LISTED OR MEET MINIMUM STANDARDS FOR TRANSFER OF
 POWER. NEC 702.4,702.5 ( ALL) , 702.6, 90.7, 110.3 ETC
  
 7) NOTE: PREVIOUS REVIEW NOTES WITH RESPECT TO MINIMUM
 WIND LOADS TO BE ON PLANS PER 1609 OF THE FBC ARE NOT
 DONE. RESPONSE MENTIONS NOTES ADDED TO PLANS HOWEVER NO
 WIND LOAD INFORMATION IS ON SITE PLANS.
  
 8) NOTE: PLANS INDICATE RECEPTACLES FOR DYE PACKS ABOVE
 CEILING. HOWEVER PER 400.8(2) CORD AND PLUG CONNECTIONS
 ABOVE CEILINGS ARE NOT PERMITTED. THIS INCLUDES CORDS
 AS NOTED.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  