Plan Review Notes
Plan Review Notes For Permit 08100349
Permit Number 08100349
Review Stop E
Sequence Number 2
Notes
Date Text
2009-01-30 11:08:31** DENIED PLANS**
  
 1) NOTE: PLANS HAVE STILL ONLY BEEN SUBMITTED FOR PLAN
 REVIEW ONLY AND HAVE NOT BEEN SUBMITTED UNDER PERMIT
 APPLICATION. IN ORDER FOR PROJECT TO FALL UNDER THE
 CURRENT CODE CYCLE PERMIT APPLICATION MUST BE MADE WITH
 REQUIRED FEES PAID BEFORE MARCH 1ST, 2009.
 ALL PERMIT APPLICATIONS MADE ON THIS DATE OR AFTER WILL
 FALL UNDER THE NEW CODE CYCLES OF THE 2007 FBC.
  
 2) NOTE: THE LIFE SAFETY CODE HAS ALREADY BEEN CHANGED
 PER STATE FIRE MARSHAL AS OF DEC 31ST, 2008. THIS
 SHOULD BE NOTED ON PLANS TO READ NFPA-101 2006.
  
 3) NOTE: AS STATED ON THE PREVIOUS REVIEW. PLEASE BE
 SURE ALL INFORMATION ON THE SUBMITTED INPUT DATA REPORT
 WHICH IS PART OF THE ENERGY CALCULATIONS COORDINATES
 WITH THE SUBMITTED PLANS. AS NOTED PREVIOUSLY, THE
 NUMBER OF FIXTURES, THE TYPES OF FIXTURES, THE WATTAGE
 OF FIXTURES ETC ARE ALL REQUIRED TO MATCH WITH THE
 SUBMITTED PLANS.
 ONE EXAMPLE GIVEN BELOW OF ITEMS WHICH ARE NOT CODE
 COMPLIANT ON THE SUBMITTED CALCULATIONS IS THE EXTERIOR
 LIGHTING. THE IDR ONLY INDICATES A TOTAL OF 3 LIGHT
 FIXTURES ALL BEING THE SAME WATTAGE. THIS IS NOT
 POSSIBLE AS THE SUBMITTED PLANS CONTAIN ALMOST TWO
 DOZEN FIXTURES AND NOT ALL OF THESE ARE THE SAME TYPE
 OF FIXTURE.
 PLEASE REVISE AND UPDATE CALCULATIONS. THIS IS ONE
 EXAMPLE ONLY AND IS NOT A LIST OF ALL POSSIBLE ITEMS.
 PLEASE SEE WATER HEATER AS ANOTHER.
 13-415.2.ABC.1.1,.1.2 AND .1.3
 13-412.1.ABC.3.4.1
 ** ALSO SEE NOTES WITH RESPECT TO FLOORING IN EVERY
 AREA OF THE ENTIRE BUILDING WHICH IS WHAT IS SHOWN ON
 THE IDR FOR ALL FLOORS. THIS WILL AFFECT THE ELECTRICAL
 SERVICE EQUIPMENT AS WELL AS PANELS.
  
 4) NOTE: PLEASE PROVIDE LISTING OF THE PROPOSED MANUAL
 TRANSFER SWITCH. IS THIS A LISTED 1008 ENCLOSURE? COULD
 NOT LOCATE LISTING AS A AUTOMATIC OR MANUAL ON PRODUCT
 DATA SUBMITTED.
 702.6,110.3,90.7
  
 5) NOTE: ON THE PREVIOUS REVIEW A REQUEST WAS MADE TO
 PROVIDE PRODUCT DATA SHEETS FOR THE PROPOSED UPS. THESE
 SHEETS NEEDED TO INDICATE A LISTING FROM A NRTL. THIS
 OFFICE/REVIEWER COULD NOT LOCATE ANY LISTING FROM ANY
 NRTL ON THE DOCUMENTS SUBMITTED.
 110.3,90.7, FBC 106.1.1, 106.1.2 FOR ADDITIONAL
 INFORMATION AND COORDINATION
  
 6) NOTE: AS BRIEFLY NOTED ABOVE IN NOTE #3 THE IDR OF
 THE ENERGY CALCULATIONS FOR FLOORS STATES CARPET AND
 RUBBER PADDING FOR ALL AREAS AND FLOORS OF THE
 BUILDING. THIS IS NOT POSSIBLE AS CARPET AND RUBBER
 PADDING IS NOT PERMITTED IN THE AREAS WHERE THE
 ELECTRICAL PANELS AND OVER CURRENT PROTECTION IS
 LOCATED.
 240.24,408.36 ETC
  
 7) NOTE: PLEASE SEE 13-415.1.ABC.1.2 FOR REQUIRED
 CONTROLS FOR BREAK ROOM OR CONFERENCE ROOMS. THIS IS
 ABOVE THE REQUIREMENT FOR BUILDINGS GREAT THAN 5K SQ
 FT.
 ** NOTE IDR FOR CONTROL METHODS*
  
 8) NOTE: PLEASE COMPLETE ELECTRICAL PLANS AS NOTED ON
 PREVIOUS REVIEW. THE SITE LIGHTING PLANS FOR EXAMPLE DO
 NOT SHOW ANY CIRCUITING. THESE ARE NOT FIGURED INTO THE
 ENERGY CALCULATIONS.
 240.4,310.16,408.4,220, FBC 13-415.1.ABC.1.4,
 13-415.2.ABC.1.3
 **
 PLEASE SEE COMMENTS WITH RESPECT TO MINIMUM DESIGN FOR
 WIND LOADS PER TABLE 1609. THE SITE LIGHTING PLANS NEED
 TO SHOW MINIMUM WIND LOADS. CALCULATIONS WILL BE
 REQUIRED FOR ANY POLE LIGHTING SEPARATELY UNDER
 BUILDING REVIEW.
  
 9) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE LISTED
 ON THE ELECTRICAL PLANS.
 2004 FBC W/ 2007 REVISIONS.
 2005 NFPA-70
  
 10) NOTE: PLEASE BE SURE ALL PANEL SCHEDULES ARE
 SPECIFIC TO ROOMS AND AREAS IN WHICH THEY FEED. FOR
 EXAMPLE: INSTEAD OF *RECEPTACLES OFFICE* THIS WOULD
 ACTUALLY LIST THE ACTUAL DESIGNATION OF EACH OF THE
 ROOMS. PLEASE BE SURE ALL ROOMS CONTAIN EITHER ALPHA OR
 NUMERIC DESIGNATIONS.
  
 11) NOTE: AS PROJECT HAS NOT APPLIED FOR PERMIT
 VALUATION CAN NOT BE CONFIRMED PER FBC108.3.
  
  
  
  
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  