2009-01-30 11:08:31 | ** DENIED PLANS** |
| |
| 1) NOTE: PLANS HAVE STILL ONLY BEEN SUBMITTED FOR PLAN |
| REVIEW ONLY AND HAVE NOT BEEN SUBMITTED UNDER PERMIT |
| APPLICATION. IN ORDER FOR PROJECT TO FALL UNDER THE |
| CURRENT CODE CYCLE PERMIT APPLICATION MUST BE MADE WITH |
| REQUIRED FEES PAID BEFORE MARCH 1ST, 2009. |
| ALL PERMIT APPLICATIONS MADE ON THIS DATE OR AFTER WILL |
| FALL UNDER THE NEW CODE CYCLES OF THE 2007 FBC. |
| |
| 2) NOTE: THE LIFE SAFETY CODE HAS ALREADY BEEN CHANGED |
| PER STATE FIRE MARSHAL AS OF DEC 31ST, 2008. THIS |
| SHOULD BE NOTED ON PLANS TO READ NFPA-101 2006. |
| |
| 3) NOTE: AS STATED ON THE PREVIOUS REVIEW. PLEASE BE |
| SURE ALL INFORMATION ON THE SUBMITTED INPUT DATA REPORT |
| WHICH IS PART OF THE ENERGY CALCULATIONS COORDINATES |
| WITH THE SUBMITTED PLANS. AS NOTED PREVIOUSLY, THE |
| NUMBER OF FIXTURES, THE TYPES OF FIXTURES, THE WATTAGE |
| OF FIXTURES ETC ARE ALL REQUIRED TO MATCH WITH THE |
| SUBMITTED PLANS. |
| ONE EXAMPLE GIVEN BELOW OF ITEMS WHICH ARE NOT CODE |
| COMPLIANT ON THE SUBMITTED CALCULATIONS IS THE EXTERIOR |
| LIGHTING. THE IDR ONLY INDICATES A TOTAL OF 3 LIGHT |
| FIXTURES ALL BEING THE SAME WATTAGE. THIS IS NOT |
| POSSIBLE AS THE SUBMITTED PLANS CONTAIN ALMOST TWO |
| DOZEN FIXTURES AND NOT ALL OF THESE ARE THE SAME TYPE |
| OF FIXTURE. |
| PLEASE REVISE AND UPDATE CALCULATIONS. THIS IS ONE |
| EXAMPLE ONLY AND IS NOT A LIST OF ALL POSSIBLE ITEMS. |
| PLEASE SEE WATER HEATER AS ANOTHER. |
| 13-415.2.ABC.1.1,.1.2 AND .1.3 |
| 13-412.1.ABC.3.4.1 |
| ** ALSO SEE NOTES WITH RESPECT TO FLOORING IN EVERY |
| AREA OF THE ENTIRE BUILDING WHICH IS WHAT IS SHOWN ON |
| THE IDR FOR ALL FLOORS. THIS WILL AFFECT THE ELECTRICAL |
| SERVICE EQUIPMENT AS WELL AS PANELS. |
| |
| 4) NOTE: PLEASE PROVIDE LISTING OF THE PROPOSED MANUAL |
| TRANSFER SWITCH. IS THIS A LISTED 1008 ENCLOSURE? COULD |
| NOT LOCATE LISTING AS A AUTOMATIC OR MANUAL ON PRODUCT |
| DATA SUBMITTED. |
| 702.6,110.3,90.7 |
| |
| 5) NOTE: ON THE PREVIOUS REVIEW A REQUEST WAS MADE TO |
| PROVIDE PRODUCT DATA SHEETS FOR THE PROPOSED UPS. THESE |
| SHEETS NEEDED TO INDICATE A LISTING FROM A NRTL. THIS |
| OFFICE/REVIEWER COULD NOT LOCATE ANY LISTING FROM ANY |
| NRTL ON THE DOCUMENTS SUBMITTED. |
| 110.3,90.7, FBC 106.1.1, 106.1.2 FOR ADDITIONAL |
| INFORMATION AND COORDINATION |
| |
| 6) NOTE: AS BRIEFLY NOTED ABOVE IN NOTE #3 THE IDR OF |
| THE ENERGY CALCULATIONS FOR FLOORS STATES CARPET AND |
| RUBBER PADDING FOR ALL AREAS AND FLOORS OF THE |
| BUILDING. THIS IS NOT POSSIBLE AS CARPET AND RUBBER |
| PADDING IS NOT PERMITTED IN THE AREAS WHERE THE |
| ELECTRICAL PANELS AND OVER CURRENT PROTECTION IS |
| LOCATED. |
| 240.24,408.36 ETC |
| |
| 7) NOTE: PLEASE SEE 13-415.1.ABC.1.2 FOR REQUIRED |
| CONTROLS FOR BREAK ROOM OR CONFERENCE ROOMS. THIS IS |
| ABOVE THE REQUIREMENT FOR BUILDINGS GREAT THAN 5K SQ |
| FT. |
| ** NOTE IDR FOR CONTROL METHODS* |
| |
| 8) NOTE: PLEASE COMPLETE ELECTRICAL PLANS AS NOTED ON |
| PREVIOUS REVIEW. THE SITE LIGHTING PLANS FOR EXAMPLE DO |
| NOT SHOW ANY CIRCUITING. THESE ARE NOT FIGURED INTO THE |
| ENERGY CALCULATIONS. |
| 240.4,310.16,408.4,220, FBC 13-415.1.ABC.1.4, |
| 13-415.2.ABC.1.3 |
| ** |
| PLEASE SEE COMMENTS WITH RESPECT TO MINIMUM DESIGN FOR |
| WIND LOADS PER TABLE 1609. THE SITE LIGHTING PLANS NEED |
| TO SHOW MINIMUM WIND LOADS. CALCULATIONS WILL BE |
| REQUIRED FOR ANY POLE LIGHTING SEPARATELY UNDER |
| BUILDING REVIEW. |
| |
| 9) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE LISTED |
| ON THE ELECTRICAL PLANS. |
| 2004 FBC W/ 2007 REVISIONS. |
| 2005 NFPA-70 |
| |
| 10) NOTE: PLEASE BE SURE ALL PANEL SCHEDULES ARE |
| SPECIFIC TO ROOMS AND AREAS IN WHICH THEY FEED. FOR |
| EXAMPLE: INSTEAD OF *RECEPTACLES OFFICE* THIS WOULD |
| ACTUALLY LIST THE ACTUAL DESIGNATION OF EACH OF THE |
| ROOMS. PLEASE BE SURE ALL ROOMS CONTAIN EITHER ALPHA OR |
| NUMERIC DESIGNATIONS. |
| |
| 11) NOTE: AS PROJECT HAS NOT APPLIED FOR PERMIT |
| VALUATION CAN NOT BE CONFIRMED PER FBC108.3. |
| |
| |
| |
| |
| |
| |
| |
| ** IMPORTANT ** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| INTO TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |