Plan Review Notes
Plan Review Notes For Permit 08100349
Permit Number 08100349
Review Stop P
Sequence Number 1
Notes
Date Text
2008-11-03 14:53:15DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 CITY WPB MUNICIPAL CODES
  
 1. ALL SHEETS. THE TITLE BLOCKS SHALL INDICATE THE
 CORRECT ADDRESS WHICH IS 8132 OKEECHOBEE BLVD, NOT JUST
 OKEECHOBEE ROAD AS SHOWN. SECTION 106.1.1.
  
 2. SHT AO THE CODE INFORMATION SHALL INCLUDE THE 2005,
 2006 & 2007 REVISIONS/AMENDMENTS. SECTION 106.1.1.
  
 3. SHT A1 THE SINK IN ROOM 111 SHALL BE ACCESSIBLE.
 PLEASE SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTION
 11-4.24 WITH ALL SUBSECTIONS. FORWARD APPROACH CLEAR
 FLOOR SPACE IS REQUIRED AND CABINET DOORS ARE NOT
 APPROVED IN THE CLEAR FLOOR SPACE.
  
 4. SHTS A3 & A4.1 INDICATE THE SIZE OF THE GUTTERS AND
 DOWNSPOUTS. TABLES 1106.3 & 1106.6.
  
 5. SHT A8 DETAILS 8 & 10 SHOW COMPLIANCE WITH THE
 FOLLOWING:
 ___W/C'S:
 A. 11-4.16.5 FLUSH CONTROLS (SHOWN ON WALL SIDE).
 ___LAVS:
 A. 11-4.19.2 CLEARANCES
 B. 11-4.19.7 FAUCETS
  
 6. SHT A8 DETAILS 8 & 9. PER SECTION 1210.2 WALLS
 WITHIN 2 FEET OF URINALS AND WATER CLOSETS SHALL HAVE A
 SMOOTH, HARD, NONABSORBENT SURFACE UP TO 4 FEET. 3 FT 4
 INCHES IS SHOWN.
  
 7. SHT A10 ELEVATION 5. SHOW COMPLIANCE WITH SECTION
 11-4.24. (SEE COMMENT 3).
  
 8. ALL P, M & E SHEETS. PER FAC 61G15-23.002(1)(2) A
 PROFESSIONAL ENGINEER SHALL SIGN HIS NAME & AFFIX HIS
 SEAL TO ALL PLANS. IT APPEARS THAT AN INITIAL HAS BEEN
 USED IN PLACE OF THE REQUIRED SIGNATURE. IF INDEED THIS
 IS THE LEGAL SIGNATURE OF THE ENGINEER OF RECORD, THEN
 A SIGNED, SEALED, DATED, NOTORIZED LETTER INDICATING
 THE LEGAL SIGNATURE FOR OUR RECORDS SHALL BE SUBMITTED.
 FS 471.025.
  
 9. SHT P-1 FD-2 IN THE MECHANICAL ROOM IS NOT APPROVED
 FOR CONDENSATE DRAINAGE. ARTICLE III SECTION
 90-125(B)(5) . PLEASE SUBMIT INFORMATION/RISER SHOWING
 THE APPROVED DISPOSAL OF THE CONDENSATE. (PLANTED AREA,
 STORM LINE, DRYWELL ETC.) (MINIMUM 1 FOOT OFF STRUCTURE
 WALL REQUIRED. 1503.6).
  
 10. SHT P1 PLUMBING FLOOR PLAN DOES NOT SHOW THE RISER
 AND PIPING FOR THE LAVS AS INDICATED ON THE WASTE &
 VENT RISER DIAGRAM. PLEASE SHOW THE SANT. PIPING AND
 RISER FOR THE LAVS ON THE FLOOR PLAN TO CORRELATE WITH
 THE RISER DIAGRAM. SECTIONS 106.1.1 & 701.1.
  
 11. SHT P2 THE WATER HAMMER ARRESTORS SHALL BE
 INSTALLED NEAR THE FIXTURES IN AN EFFECTIVE RANGE NOT
 IN THE CEILING AS SHOWN. PDI-WH 201.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  