2008-10-23 12:05:28PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 FOR PLAN REVIEW NOT FOR PERMIT.
 *** DENIED ***
  
 1) ENERGY CALCULATIONS SYSTEM REPORT NEEDS TO LIST EACH
 SYSTEM INDIVIDUALITY NOT COMBINE THEM TOGETHER, PER
 2004 FBC 13-407.2.A.
  
 2) PLEASE SUBMIT COOLING LOAD CALCULATIONS, PER 2004
 FBC 13-407.1.ABC.1.
  
 3) A/C SYSTEM HP-1 HP-2 WITH AHU-1 AND CU-1 WITH AC-1
 MODEL NUMBERS LISTED ON THE A/C EQUIPMENT SCHEDULE
 COULD NOT BE FOUND ON THE ARI DIRECTORY WEB-SITE,
 PLEASE SUBMIT AN ARI CERTIFICATE OR MANUFACTURE SPEC.
 SHEETS, PER 2004 FBC 13-407.1.ABC.3.1.1.
  
 4) PLAN M0 AIR HANDLER SCHEDULE NOTE STATES ROUTE
 CONDENSATE PIPE TO FLOOR DRAIN, PLAN M1 SECTION 'A-A'
 STATES CONDENSATE LINE TO FLOOR DRAIN, AND PLAN M2
 CEILING HUNG A/H DETAIL STATES CONDENSATE DRAIN TO MOP
 SINK. PLEASE REMOVE THESE NOTES FROM THE PLANS AS
 CONDENSATE WATER MAY NOT DISCHARGE INTO THE CITY'S
 WASTE WATER FACILITY, PER CITY OF WEST PALM BEACH CITY
 CODE 90-125 (B) (5). PLEASE SHOW ON PLANS FOR
 CONDENSATE WATER TO DISCHARGE OUTDOORS TO AN
 APPROPRIATE LOCATION, PER 2004 FBC/M 307.2.1.
  
 5) AHU-1 AND AHU-2 WILL REQUIRE SMOKE DETECTORS AT THE
 SUPPLY AND RETURN, PER 2004 FBC 606.2.2 COMMON SUPPLY,
 RETURN AIR AND SUPPLY AIR SYSTEMS. WHERE MULTIPLE
 AIR-HANDLING SYSTEMS SHARE COMMON SUPPLY OR RETURN AIR
 DUCTS OR PLENUMS WITH A COMBINED DESIGN CAPACITY
 GREATER THAN 2,000 CFM (0.9 M 3 /S), THE RETURN AIR AND
 SUPPLY AIR SYSTEM SHALL BE PROVIDED WITH SMOKE
 DETECTORS IN ACCORDANCE WITH SECTION 606.2.1. PLEASE
 SHOW ON MECHANICAL PLAN.
  
 6) PLEASE ADD A NOTE TO PLAN M1. PER 2004 FBC/M 602.2.1
 MATERIALS EXPOSED WITHIN PLENUMS. EXCEPT AS REQUIRED BY
 SECTIONS 602.2.1.1 THROUGH 602.2.1.5 , MATERIALS
 EXPOSED WITHIN PLENUMS SHALL BE NONCOMBUSTIBLE OR SHALL
 HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 25 AND A
 SMOKE-DEVELOPED INDEX OF NOT MORE THAN 50 WHEN TESTED
 IN ACCORDANCE WITH ASTM E 84.
  
 7) PLEASE SUBMIT PRODUCT APPROVAL OR AN NOA FOR
 ENERTECH DC-FL LOUVERS, PER FS 553.842(1) AND FAC RULE
 9B-72, 9B-72.005, AND FAC 9B-72.010(31)(G).
  
 **PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG.
  
 *** PRODUCT APPROVALS AND NOA'S SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL (A SHOP REVIEW
 STAMP AND SIGNATURE WILL MEET THIS REQUIREMENT). SEE
 W.P.B. AMEND. 106.3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]