2008-10-23 12:05:28 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM |
| BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA |
| ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES |
| (F.S.). |
| |
| FOR PLAN REVIEW NOT FOR PERMIT. |
| *** DENIED *** |
| |
| 1) ENERGY CALCULATIONS SYSTEM REPORT NEEDS TO LIST EACH |
| SYSTEM INDIVIDUALITY NOT COMBINE THEM TOGETHER, PER |
| 2004 FBC 13-407.2.A. |
| |
| 2) PLEASE SUBMIT COOLING LOAD CALCULATIONS, PER 2004 |
| FBC 13-407.1.ABC.1. |
| |
| 3) A/C SYSTEM HP-1 HP-2 WITH AHU-1 AND CU-1 WITH AC-1 |
| MODEL NUMBERS LISTED ON THE A/C EQUIPMENT SCHEDULE |
| COULD NOT BE FOUND ON THE ARI DIRECTORY WEB-SITE, |
| PLEASE SUBMIT AN ARI CERTIFICATE OR MANUFACTURE SPEC. |
| SHEETS, PER 2004 FBC 13-407.1.ABC.3.1.1. |
| |
| 4) PLAN M0 AIR HANDLER SCHEDULE NOTE STATES ROUTE |
| CONDENSATE PIPE TO FLOOR DRAIN, PLAN M1 SECTION 'A-A' |
| STATES CONDENSATE LINE TO FLOOR DRAIN, AND PLAN M2 |
| CEILING HUNG A/H DETAIL STATES CONDENSATE DRAIN TO MOP |
| SINK. PLEASE REMOVE THESE NOTES FROM THE PLANS AS |
| CONDENSATE WATER MAY NOT DISCHARGE INTO THE CITY'S |
| WASTE WATER FACILITY, PER CITY OF WEST PALM BEACH CITY |
| CODE 90-125 (B) (5). PLEASE SHOW ON PLANS FOR |
| CONDENSATE WATER TO DISCHARGE OUTDOORS TO AN |
| APPROPRIATE LOCATION, PER 2004 FBC/M 307.2.1. |
| |
| 5) AHU-1 AND AHU-2 WILL REQUIRE SMOKE DETECTORS AT THE |
| SUPPLY AND RETURN, PER 2004 FBC 606.2.2 COMMON SUPPLY, |
| RETURN AIR AND SUPPLY AIR SYSTEMS. WHERE MULTIPLE |
| AIR-HANDLING SYSTEMS SHARE COMMON SUPPLY OR RETURN AIR |
| DUCTS OR PLENUMS WITH A COMBINED DESIGN CAPACITY |
| GREATER THAN 2,000 CFM (0.9 M 3 /S), THE RETURN AIR AND |
| SUPPLY AIR SYSTEM SHALL BE PROVIDED WITH SMOKE |
| DETECTORS IN ACCORDANCE WITH SECTION 606.2.1. PLEASE |
| SHOW ON MECHANICAL PLAN. |
| |
| 6) PLEASE ADD A NOTE TO PLAN M1. PER 2004 FBC/M 602.2.1 |
| MATERIALS EXPOSED WITHIN PLENUMS. EXCEPT AS REQUIRED BY |
| SECTIONS 602.2.1.1 THROUGH 602.2.1.5 , MATERIALS |
| EXPOSED WITHIN PLENUMS SHALL BE NONCOMBUSTIBLE OR SHALL |
| HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 25 AND A |
| SMOKE-DEVELOPED INDEX OF NOT MORE THAN 50 WHEN TESTED |
| IN ACCORDANCE WITH ASTM E 84. |
| |
| 7) PLEASE SUBMIT PRODUCT APPROVAL OR AN NOA FOR |
| ENERTECH DC-FL LOUVERS, PER FS 553.842(1) AND FAC RULE |
| 9B-72, 9B-72.005, AND FAC 9B-72.010(31)(G). |
| |
| **PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION |
| AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE |
| FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE |
| SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. |
| PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT |
| IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT |
| HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR |
| LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE |
| 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG. |
| |
| *** PRODUCT APPROVALS AND NOA'S SHALL BE REVIEWED AND |
| APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| SUBMITTAL FOR JURISDICTIONAL APPROVAL (A SHOP REVIEW |
| STAMP AND SIGNATURE WILL MEET THIS REQUIREMENT). SEE |
| W.P.B. AMEND. 106.3. |
| |
| MECHANICAL PLAN REVIEW BY; |
| TOM GORDON (561) 805-6729 |
| E-MAIL; [email protected] |