2008-11-12 10:59:20 | ***DENIED*** |
| |
| PLANS HAVE BEEN SUBMITTED FOR PLAN REVIEW AND NOT FOR |
| PERMIT |
| |
| 1) CS SHEET IDENTIFIES ADDRESS AS OKEECHOBEE ROAD. |
| PLEASE CORRECT ADDRESS TO READ OKEECHOBEE BLVD. AND ADD |
| NUMERICAL OF BUILDING. |
| |
| 2) ADDRESS OF PROJECT TO BE PROVIDED IN TITLE BLOCK OF |
| EACH SHEET SUBMITTED. |
| |
| 3) PROVISIONS FOR AFTER NORMAL BUSINESS HOURS ACCESS TO |
| BE ADDRESSED EITH BY KNOX BOX ENTRY SYSTEM OR OTHER |
| APPROVED SECURED MEANS. |
| |
| 4) ADDRESS IS REQUIRED ON BUILDING THAT SHALL BE |
| MINIMUM OF 6" IN HEIGHT, 1" WIDTH AND CONTRASTING WITH |
| BACKGROUND. PLEASE ADD NOTE TO ELEVATIONS ON SHEET A3. |
| |
| 5) MINIMUM 2A-10B,C RATED FIRE EXTINGUISHERS ARE |
| REQUIRED TO BE MOUNTED AT LOCATIONS NOT TO EXCEED |
| MINIMUM 75' TRAVEL DISTANCE REQUIREMENT. |
| |
| 6) INDICATE THE MINIMUM INTERIOR FINISH CLASSIFICATION |
| FOR WALLS AND CEILING PER 101, SEC. 38.3.3.2. |
| |
| 7) DUCT SMOKE DETECTORS SHALL BE TIED INTO THE BUILDING |
| FIRE ALARM SYSTEM WHEN APPLICABLE. IF NO FIRE ALARM |
| SYSTEM IS PROVIDED, AUDIBLE/VISUAL APPLIANCES ARE STILL |
| REQUIRED FOR LOCAL OCCUPANT NOTIFICATION. |
| |
| 8) ALL EXIT DOORS SHALL COMPLY WITH 101, SEC. 7.2.1.5 |
| LOCKS, LATCHES AND ALARMS. |
| |
| 9) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY |
| WITH NFPA 241. |
| |
| |
| ALTHOUGH NOT A REQUIREMENT, A RESPONSE LETTER |
| INDICATING HOW AND WHERE ON EACH SHEET EACH COMMENT WAS |
| ADDRESSED WOULD HELP TO EXPEDITE THE PLAN REVIEW |
| PROCESS. |
| |
| |
| MIKE WENNERGREN, ASST. FIRE MARSHAL |
| FIRE PLAN REVIEW |
| FIRE PREVENTION (561) 804-4756 |
| |
| |
| |
| |
| |
| |
| |
| |
| |