Plan Review Notes
Plan Review Notes For Permit 08100349
Permit Number 08100349
Review Stop E
Sequence Number 1
Notes
Date Text
2008-10-31 17:00:53 
  
  
  
 ** DENIED REVIEW **
  
 1) NOTE: PROJECT INFORMATION HAS BEEN FORWARDED TO THE
 ADDRESSING REVIEW TO CORRECT ADDRESS DISCREPANCIES. THE
 APPLIED LOCATION IS 8132 W OKEECHOBEE BLVD HOWEVER THE
 PLANS AND OTHER SUPPORTING DOCUMENTS SUCH AS ENERGY
 CALCULATIONS STATE OKEECHOBEE ROAD WHICH IS AN ENTIRELY
 DIFFERENT LOCATION AND STREET.
 PLEASE ADJUST PLANS AND CORRECT ADDRESS ONCE FINAL
 DETERMINATION IS MADE.
 FBC 106.5
 FAC 61G1-16.004, 61G15-23.002
  
 2) NOTE: PLEASE SEE THE PLANS HAVE COME IN FOR PLAN
 REVIEW ONLY AND HAS NOT BEEN SUBMITTED FOR PERMIT. ONCE
 PLANS MEET CODE COMPLIANCE AND PERMIT APPLICATION HAS
 NOT BEEN MADE THE REVIEW WILL STILL REMAIN IN A FAILED
 STATUS UNTIL PERMIT APPLICATION IS MADE. THE LICENSING
 OF ALL DESIGNERS AND CONTRACTORS WILL BE VERIFIED AT
 THAT POINT.
  
 3) NOTE: PLEASE BE SURE THE SUBMITTED ENERGY
 CALCULATIONS AND THE INPUT DATA REPORT COORDINATES WITH
 THE SUBMITTED. PLANS. THE NUMBER OF FIXTURES, THE TYPE
 OF FIXTURES, THE WATTAGES AND THE CONTROLS NEED TO
 MATCH WITH THE PLANS.
 THE IDR SHOWS FOR INTERIOR LIGHTS A TOTAL OF THREE
 FIXTURES WHICH IS NOT POSSIBLE BASED ON THE PLANS. THE
 IDR STATES CLEARLY AT THE TOP OF THE LIGHTING FIELD ***
 NO OF LUMINAIRES*, ** WATTS PER LUMINAIRE* ETC. THIS
 DOES NOT INCLUDE ANY IDENTIFICATION OF USING JUST ONE
 FIXTURE AND A TOTAL. BASED ON THE PLANS SUBMITTED EVEN
 IF USING ONE TOTAL WATTAGE THE AMOUNT WOULD STILL NOT
 CORRELATE.
 PLEASE REVISE AND ADJUST ALL.
 PLEASE BE SURE TO SEE THE SPECIFIC SECTIONS BELOW FOR
 INTERIOR ALLOWANCES AND HOW VA LOADS OF FIXTURES AND
 ANY TRACK IS REQUIRED TO BE ENTERED.
 13-400.3A, 13-101, 13-415.2, 13-415.2.ABC.1.1, .1.2 AND
 .1.3.
  
  
 4) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE LISTED
 ON PLANS AS WELL AS ON ELECTRICAL PLANS. SOME CODES
 REFERENCES ON PLANS ARE NO LONGER ADOPTED BY THE STATE
 OF FLORIDA AND HAVE NOT BEEN FOR OVER A DECADE. PLEASE
 SEE SHEET E1 FOR EXAMPLE WHICH STATES THE *1996
 NATIONAL ELECTRICAL CODE**. PLEASE BE SURE TO CORRECT
 CODES REFLECTED ON PLANS.
 THE FOLLOWING SHALL BE LISTED AT A MINIMUM FOR THIS
 REVIEWER AND FOR THIS TRADE.
  
 2004 FBC W/ 2007 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72 (WHEN APPLICABLE)
  
 5) NOTE: ( FOR CONTRACTOR)
 THE APPLIED VALUE FOR COMPLETE SCOPE OF WORK SHALL
 INCLUDE ALL LABOR, MATERIALS, DESIGN COST, EQUIPMENT
 ETC EVEN IF ANY OF THESE ITEMS ARE OWNER SUPPLIED.
 FBC 108.3
  
 6) NOTE: PLEASE SUBMIT THE MANUFACTURE SPECS/CUT SHEETS
 FOR THE PROPOSED UPS. 90.7,110.3
  
 7) NOTE: PLEASE SUBMIT THE MANUFACTURE SPECS/CUT SHEETS
 FOR THE PROPOSED MTS. 90.7,110.3.
  
 8) NOTE: PLEASE KNOW SEPARATE SYSTEMS SUCH AS THE LOW
 VOLTAGE FOR CAMERAS, PHONE, DATA ETC SHALL BE UNDER A
 SEPARATE PERMIT. THE LV FOR SECURITY WILL ALSO BE UNDER
 A SEPARATE PERMIT. THE SECURITY SYSTEM SHOP DRAWINGS
 SHOWING SPECIFICS ARE NOT REQUIRED BY THIS OFFICE IN
 FAC T HAVING THESE PLANS ON RECORD FILE FOR PUBLIC
 ACCESS IS NOT REQUIRED. BASE PLANS SHOWING CAMERA
 LOCATIONS, ANY ACCESS CONTROLS IS REQUIRED. PLEASE CALL
 TO GO OVER SPECIFICS OR FOR ANY QUESTIONS REGARDING
 SYSTEMS.
 **FBC 105.1, 106.1.1
  
 9) NOTE: PLEASE COMPLETE PLANS WITH PANEL SCHEDULES AND
 LOAD CALCULATIONS. CIRCUITING AND OTHER ITEMS FOR CODE
 COMPLIANCE CAN NOT BE VERIFIED FOR CODE COMPLIANCE AT
 THIS TIME.
 220, 408.4, 240.4, 310.16 ETC
 FBC 106.1.1, 106.1.2
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  