2008-10-31 17:00:53 | |
| |
| |
| |
| ** DENIED REVIEW ** |
| |
| 1) NOTE: PROJECT INFORMATION HAS BEEN FORWARDED TO THE |
| ADDRESSING REVIEW TO CORRECT ADDRESS DISCREPANCIES. THE |
| APPLIED LOCATION IS 8132 W OKEECHOBEE BLVD HOWEVER THE |
| PLANS AND OTHER SUPPORTING DOCUMENTS SUCH AS ENERGY |
| CALCULATIONS STATE OKEECHOBEE ROAD WHICH IS AN ENTIRELY |
| DIFFERENT LOCATION AND STREET. |
| PLEASE ADJUST PLANS AND CORRECT ADDRESS ONCE FINAL |
| DETERMINATION IS MADE. |
| FBC 106.5 |
| FAC 61G1-16.004, 61G15-23.002 |
| |
| 2) NOTE: PLEASE SEE THE PLANS HAVE COME IN FOR PLAN |
| REVIEW ONLY AND HAS NOT BEEN SUBMITTED FOR PERMIT. ONCE |
| PLANS MEET CODE COMPLIANCE AND PERMIT APPLICATION HAS |
| NOT BEEN MADE THE REVIEW WILL STILL REMAIN IN A FAILED |
| STATUS UNTIL PERMIT APPLICATION IS MADE. THE LICENSING |
| OF ALL DESIGNERS AND CONTRACTORS WILL BE VERIFIED AT |
| THAT POINT. |
| |
| 3) NOTE: PLEASE BE SURE THE SUBMITTED ENERGY |
| CALCULATIONS AND THE INPUT DATA REPORT COORDINATES WITH |
| THE SUBMITTED. PLANS. THE NUMBER OF FIXTURES, THE TYPE |
| OF FIXTURES, THE WATTAGES AND THE CONTROLS NEED TO |
| MATCH WITH THE PLANS. |
| THE IDR SHOWS FOR INTERIOR LIGHTS A TOTAL OF THREE |
| FIXTURES WHICH IS NOT POSSIBLE BASED ON THE PLANS. THE |
| IDR STATES CLEARLY AT THE TOP OF THE LIGHTING FIELD *** |
| NO OF LUMINAIRES*, ** WATTS PER LUMINAIRE* ETC. THIS |
| DOES NOT INCLUDE ANY IDENTIFICATION OF USING JUST ONE |
| FIXTURE AND A TOTAL. BASED ON THE PLANS SUBMITTED EVEN |
| IF USING ONE TOTAL WATTAGE THE AMOUNT WOULD STILL NOT |
| CORRELATE. |
| PLEASE REVISE AND ADJUST ALL. |
| PLEASE BE SURE TO SEE THE SPECIFIC SECTIONS BELOW FOR |
| INTERIOR ALLOWANCES AND HOW VA LOADS OF FIXTURES AND |
| ANY TRACK IS REQUIRED TO BE ENTERED. |
| 13-400.3A, 13-101, 13-415.2, 13-415.2.ABC.1.1, .1.2 AND |
| .1.3. |
| |
| |
| 4) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE LISTED |
| ON PLANS AS WELL AS ON ELECTRICAL PLANS. SOME CODES |
| REFERENCES ON PLANS ARE NO LONGER ADOPTED BY THE STATE |
| OF FLORIDA AND HAVE NOT BEEN FOR OVER A DECADE. PLEASE |
| SEE SHEET E1 FOR EXAMPLE WHICH STATES THE *1996 |
| NATIONAL ELECTRICAL CODE**. PLEASE BE SURE TO CORRECT |
| CODES REFLECTED ON PLANS. |
| THE FOLLOWING SHALL BE LISTED AT A MINIMUM FOR THIS |
| REVIEWER AND FOR THIS TRADE. |
| |
| 2004 FBC W/ 2007 REVISIONS. |
| 2005 NFPA-70 |
| 2003 NFPA-101 |
| 2002 NFPA-72 (WHEN APPLICABLE) |
| |
| 5) NOTE: ( FOR CONTRACTOR) |
| THE APPLIED VALUE FOR COMPLETE SCOPE OF WORK SHALL |
| INCLUDE ALL LABOR, MATERIALS, DESIGN COST, EQUIPMENT |
| ETC EVEN IF ANY OF THESE ITEMS ARE OWNER SUPPLIED. |
| FBC 108.3 |
| |
| 6) NOTE: PLEASE SUBMIT THE MANUFACTURE SPECS/CUT SHEETS |
| FOR THE PROPOSED UPS. 90.7,110.3 |
| |
| 7) NOTE: PLEASE SUBMIT THE MANUFACTURE SPECS/CUT SHEETS |
| FOR THE PROPOSED MTS. 90.7,110.3. |
| |
| 8) NOTE: PLEASE KNOW SEPARATE SYSTEMS SUCH AS THE LOW |
| VOLTAGE FOR CAMERAS, PHONE, DATA ETC SHALL BE UNDER A |
| SEPARATE PERMIT. THE LV FOR SECURITY WILL ALSO BE UNDER |
| A SEPARATE PERMIT. THE SECURITY SYSTEM SHOP DRAWINGS |
| SHOWING SPECIFICS ARE NOT REQUIRED BY THIS OFFICE IN |
| FAC T HAVING THESE PLANS ON RECORD FILE FOR PUBLIC |
| ACCESS IS NOT REQUIRED. BASE PLANS SHOWING CAMERA |
| LOCATIONS, ANY ACCESS CONTROLS IS REQUIRED. PLEASE CALL |
| TO GO OVER SPECIFICS OR FOR ANY QUESTIONS REGARDING |
| SYSTEMS. |
| **FBC 105.1, 106.1.1 |
| |
| 9) NOTE: PLEASE COMPLETE PLANS WITH PANEL SCHEDULES AND |
| LOAD CALCULATIONS. CIRCUITING AND OTHER ITEMS FOR CODE |
| COMPLIANCE CAN NOT BE VERIFIED FOR CODE COMPLIANCE AT |
| THIS TIME. |
| 220, 408.4, 240.4, 310.16 ETC |
| FBC 106.1.1, 106.1.2 |
| |
| |
| |
| |
| **IMPORTANT** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| INTO TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
| |