2009-01-20 11:23:45REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. COOLING LOAD CALCULATIONS WERE NOT PROVIDED WITH
 THIS SUBMISSION. COOLING LOAD CALCULATIONS SHALL BE
 APPENDED TO THE ENERGY CALCULATIONS IN ACCORDANCE WITH
 FBCB 13-407.1.ABC.1.1.
  
 2. OUTSIDE AIR CALCULATIONS DO NOT CORRESPOND WITH THE
 REQUIREMENTS OF FBCM TABLE 403.3. THE OCCUPANCY
 CLASSIFICATION AND OCCUPANT LOAD AS STATED IN THE TABLE
 SHALL BE USED WHEN CALCULATING OUTSIDE AIR
 REQUIREMENTS. ALSO, THE PLANS SHOW THE 150 CFM OF
 EXHAUST AS ADDED TO THE OUTSIDE AIR FOR THE TOTAL. THE
 INCLUSION OF EXHAUST IN THE BATHROOMS DOES NOT INCREASE
 THE AMOUNT OF OUTSIDE AIR SUPPLIED AND SHOULD NOT BE
 PART OF THE TOTAL.
  
 3. THSES PLANS WERE DRAWN AND DESIGNED BY AN AC
 CONTRACTOR. THIS PROJECT IS FOR A BUILDING WITH AN
 OCCUPANT LOAD IN EXESS OF 100 PERSONS AND THEREFOR
 REQUIRES THE SYSTEMS TO BE DESIGNED BY AN ENGINEER IN
 ACCORDANCE WITH FLORIDA STATUTE 471.003. PROVIDE AC
 PLANS SIGNED AND SEALED BY A PROFESSIONAL ENGINEER
 LICENSED IN ACCORDANCE WITH THIS STATUTE.
  
 4. PLEASE SEE ELECTRICAL COMMENTS REGARDING THE VERSION
 OF ENERGY CALCULATIONS WHICH WERE SUBMITTED.
  