Date |
Text |
2008-10-30 15:40:05 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| |
| 1. SHT 6 THE ACCESSIBLE STALLS SHALL COMPLY WITH FIGURE |
| 11-30E. 5 FEET OF CLEAR FLOOR SPACE FROM THE WALL |
| ADJACENT TO THE W/C TO THE LAV, AND THE LAV SHALL BE A |
| MINIMUM 15 INCHES OFF THE WALL. AS INDICATED THE LAV IS |
| NOT SHOWN AS 15" OFF THE WALL TO THE CENTERLINE OF THE |
| FIXTURE. THE OPENING FOR THE LAV IS INDICATED AS 1'8". |
| IF THE LAV WERE TO BE 15" OFF THE WALL AS REQUIRED, THE |
| LAV WOULD BE IN THE 5 FT CLEAR FLOOR SPACE OF THE W/C |
| WHICH IS NOT APPROVED. (SEE RECOMMENDATION FOR LAYOUT |
| CHANGE OF STALL IN WOMEN'S TOILET ROOM). |
| |
| 2. SHT 6 DETAIL FOR THE DRINKING FOUNTAIN DOES NOT SHOW |
| COMPLIANCE WITH 11-4.1.3(10)(A) PROVISIONS FOR THOSE |
| WHO HAVE DIFFICULTY BENDING OR STOOPING. PLEASE |
| INDICATE A CUP DISPENSER ADJACENT TO THE DRINKING |
| FOUNTAIN. |
| |
| 3. SHT 1 THE WATER RISER DIAGRAM DOES NOT REFLECT THE |
| FLOOR PLAN. PLEASE SUBMIT A WATER RISER DIAGRAM THAT |
| REFLECTS THE LOCATION OF THE FIXTURES ON THE FLOOR |
| PLAN. SECTION 106.3.5.1.3. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |