Plan Review Notes For Permit 08100329 |
Permit Number |
08100329 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-10-31 15:35:58 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | (F.S.). | | | | *** DENIED *** | | | | 1) SHOW ON MECHANICAL PLAN HOW THE OUTDOOR AIR IS | | GETTING TO THE AIR HANDLER UNIT, SEE 2004 FBC/M 401. | | | | 2) SHOW ON MECHANICAL PLAN THE BATHROOM EXHAUST FAN TO | | BE INSTALLED, PER 2004 FBC/M TABLE 403.3. PROVIDE 50 | | CFM'S PER WATER CLOSET OR URINAL. | | | | 3) OUTDOOR AIR CALCULATIONS ARE SHOWING RESTROOM | | EXHAUST TOTALING 100 CFM'S AS THERE ARE THREE WATER | | CLOSETS ON THE PLAN THAT NEEDS TO BE CORRECTED, PER | | 2004 FBC/M TABLE 403.3. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|