2008-10-31 15:35:58PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
  
 1) SHOW ON MECHANICAL PLAN HOW THE OUTDOOR AIR IS
 GETTING TO THE AIR HANDLER UNIT, SEE 2004 FBC/M 401.
  
 2) SHOW ON MECHANICAL PLAN THE BATHROOM EXHAUST FAN TO
 BE INSTALLED, PER 2004 FBC/M TABLE 403.3. PROVIDE 50
 CFM'S PER WATER CLOSET OR URINAL.
  
 3) OUTDOOR AIR CALCULATIONS ARE SHOWING RESTROOM
 EXHAUST TOTALING 100 CFM'S AS THERE ARE THREE WATER
 CLOSETS ON THE PLAN THAT NEEDS TO BE CORRECTED, PER
 2004 FBC/M TABLE 403.3.
  