Date |
Text |
2008-10-27 11:14:13 | BUILDING PLAN REVIEW |
| PERMIT: 08100329 |
| ADD: 909 3RD ST |
| CONT: NEWBOLD CONSTRUCTION |
| TEL: (561)644-5764 |
| |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2007 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVIEW |
| ACTION: DENIED |
| |
| 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| 1B) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT, |
| TO BE FILED WITH THE CLERK OF THE COURT. NOTE: |
| 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF |
| COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS |
| AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL & |
| VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF |
| COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST |
| INSPECTION. |
| |
| 1C) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST |
| TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO |
| THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS, PLEASE |
| UPDATE SHEET 1 TO THE 2007 SUPPLEMENTS TO THE 2004 FBC |
| |
| 2) SHEET 2 INDICATES A 4HR FIRE RATED WALL AND DOORS |
| CREATING A NEW BUILDING NOT AN ADDITION, IN DOING SO |
| PLEASE PROVIDE FIRE RESISTANCE RATED ASSEMBLIES FOR |
| THROUGH -PENETRATIONS. 712.3/ 712.3.1 |
| |
| 3) SHEET 2 & 3 INDICATES THE USE OF 8 INCH BLOCK AND A |
| RAKE BEAM AT THE FIRE WALL BUT THE FOUR HR RATING DOES |
| NOT GO THROUGH THE ROOF NOR THE ROOF OVERHANG, PLEASE |
| REVIEW SECTION 705.5.2 HORIZONTAL PROJECTING ELEMENTS, |
| ALSO REVIEW THE CODE COMMENTARY. |
| |
| 4) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION |
| THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE |
| OF OCCUPANCY: |
| A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS |
| DESIGNED. |
| B) THE TYPE OF CONSTRUCTION AS DEFINED IN TABLE 503, |
| CHAPTER 6, TABLE 601. |
| D) THE OCCUPANT LOAD, SEE 1004. |
| E) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED |
| F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED. |
| G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE |
| BUILDING PERMIT |
| H) SQ. FT. FOOTPRINT |
| |
| 5) PLANS DO NOT INDICATE WHAT THE FLOOR FINISH WILL BE, |
| THE ENRGY CALCULATIONS INPUT DATA REPORT INDICATES 392 |
| SQ FT OF CARPET AND PADDING, AT WHAT LOCATION? |
| ADDITIONAL INFORMATION REQUIRED.106.1.2. |
| |
| JIM WITMER C. B. O. |
| BUILDING PLAN REVIEW II |
| |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |
| E-MAIL: [email protected] |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| |
| |
| |
| |
| |