 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1
 AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 INCOMPLETE INFORMATION
  
 1} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT
 CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE
 EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS
 EQUAL TO OR GREATER THAN THE AVAILABLE FAULT.
  
 2} THERE IS NO INDICATION OF THE MAIN BREAKER RATING ON
 THE PLAN. 215.5 NEC.***THE WIRE AND GEC SIZES ARE SIZED
 FOR A 150 AMP MAIN, BUT THE NOTE MENTIONS 200 AMP RATED
 ENCLOSURE
  
 3} INDICATE THE LOCATION OF THE PANEL BEING RELOCATED
 SO THAT CLEARANCE REQUIREMENTS PER 110.26 AND
 REQUIREMENTS OF 240 CAN BE REVIEWED.
  