Date Text
2008-10-14 16:15:05 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING
  
 :1} THE AIC RATING OF THE EQUIPMENT BEING SET MUST BE
 THE SAME AS THE AIC RATING OF THE EQUIPMENT FEEDING IT.
  
 2} PROVIDE A RISER DIAGRAM AS IT CANNOT BE DETERMINED
 EXACTLY HOW THE ELECTRICAL CONNECTIONS OCCUR FROM THE
 PICTURES SUBMITTED.RE: HOW IS THE METER FED AND FROM
 WHERE, INDICATE THE GEC WHICH SHOULD PROBABLY BE TIED
 TO THE EXISTING SYSTEM DEPENDING AGAIN ON THE FEED,
 THERE SHOULD BE NO EQUIPMENT GROUND RAN TO THE FIRST
 MEANS FROM THE METER UNDER NORMAL CONDITIONS. THE RISER
 DIAGRAM WILL CLARIFY THESE COMMENTS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  