Plan Review Notes For Permit 08100246 |
Permit Number |
08100246 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-10-17 13:30:18 | | | DENIED | | | | 1) PER 1609.6.1 FBC THE SIMPLIFIED CALCULATION METHOD | | FOR WIND LOADS SHALL NOT BE USED TO DETERMINE WIND | | PRESSURES FOR BUILDINGS OVER 60 FT IN HEIGHT. PLEASE | | SUBMIT ENGINEERED CALCULATIONS | | | | 2) BE SURE TO INCLUDE THE LOCATION OF THE DOOR AND | | WINDOWS (ZONE 4 OR 5) | | | | 3) PROVIDE THE SIZE/TYPE OF MULLION AS SOME MAY NOT | | MEET DESIGN PRESSURES. | | | | 4) PROVIDE THE TYPE (EQUAL/UNEQUAL) AND TYPE OF GLAZING | | FOR THE SINGLE HUNG WINDOW UNITS THAT WILL MEET THE | | DESIGN PRESSURES INDICATED BY THE ENGINEERS | | CALCULATIONS. THE INFORMATION CAN BE STATED ON THE | | DRAWING OR MARKED IN THE PRODUCT APPROVAL. | | | | BLDG PLAN REVIEW | | ADRIAN MORSE | | 561-805-6716 | | |
|