Plan Review Notes
Plan Review Notes For Permit 08100246
Permit Number 08100246
Review Stop B
Sequence Number 1
Notes
Date Text
2008-10-17 13:30:18 
 DENIED
  
 1) PER 1609.6.1 FBC THE SIMPLIFIED CALCULATION METHOD
 FOR WIND LOADS SHALL NOT BE USED TO DETERMINE WIND
 PRESSURES FOR BUILDINGS OVER 60 FT IN HEIGHT. PLEASE
 SUBMIT ENGINEERED CALCULATIONS
  
 2) BE SURE TO INCLUDE THE LOCATION OF THE DOOR AND
 WINDOWS (ZONE 4 OR 5)
  
 3) PROVIDE THE SIZE/TYPE OF MULLION AS SOME MAY NOT
 MEET DESIGN PRESSURES.
  
 4) PROVIDE THE TYPE (EQUAL/UNEQUAL) AND TYPE OF GLAZING
 FOR THE SINGLE HUNG WINDOW UNITS THAT WILL MEET THE
 DESIGN PRESSURES INDICATED BY THE ENGINEERS
 CALCULATIONS. THE INFORMATION CAN BE STATED ON THE
 DRAWING OR MARKED IN THE PRODUCT APPROVAL.
  