2008-10-21 09:47:112004 FBC W/2007 REVISIONS
 INSTALL AWNING
  
 DENIED BY BUILDING
  
 1) PROVIDE AWNING FABRIC REMOVAL INSTRUCTIONS TO SHOW
 COMPLIANCE WITH FBC3105.4.2.1, QUICK RELEASE. THE
 INSTRUCTIONS SHOULD CONSIST OF A SERIES OF PHOTOGRAPHS.
 THIS IS TO BE APPROVED BY THE BUILDING OFFICIAL.
  
 2) PER BUILDING OFFICIAL, WE ARE TO PUT IN THE PERMIT
 FILE A LETTER, OR CONTRACTORS FORM, SIGNED BY THE OWNER
 (NOT THE TENANT) TO ACKNOWLEDGE THEIR RESPONSIBILITY TO
 HAVE THE AWNING COVER REMOVED PRIOR TO ANY WIND EVENT
 WITH PROJECTED WIND SPEEDS OF 75 MPH OR GREATER. THE
 LETTER/FORM MUST BE SIGNED BY THE OWNER BUT IT NEED NOT
 BE NOTARIZED.
  
 3) SPECIFY THE TYPE, LENGTH, SPACING AND LOCATIONS OF
 ALL FASTENERS THAT WILL BE USED TO ATTACH THE AWNING
 FRAME TO THE STRUCTURE. FBC 1604.8
  