2008-12-03 15:16:08COURTESY PARTIAL REVIEW
 ****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
  
 THIS IS A CURSORY REVIEW; LIST MAY NOT BE COMPLETE
  
 1. SEE SHEET 6, 2 1/2" EDGE DISTANCE REQUIRES A FACTOR
 OF .71. 9" SPACING HAS BEEN CIRCLED ON THE PRODUCT
 APPROVAL, 9 X .71 = 6.39, BUT INSTALLATION SCHEDULE
 SPECIFIES 7.74. SEE OTHER COMMENTS REGARDING ANCHOR
 SPACING.
  
 2. SHUTTER CONNECTION MOUNTING TYPE SHOULD CORRELATE
 WITH THE ANCHOR CHART. YOU'VE CIRCLED ANCHOR SPACING IN
 COLUMN "D", BUT HAVE SPECIFIED P-P3, NOT SURE WHAT THAT
 MEANS IN RELATION TO THE ANCHOR CHARTS.
  
 3. A DESIGN PRESSURE OF -70.6 HAS BEEN SPECIFIED,
 SHOULD USE THE ROW FOR 60 - 100. HOWEVER -70.6 IS VERY
 HIGH FOR A 15' STRUCTURE LOCATED IN EXPOSURE B. IT IS
 ACCEPTABLE TO EXCEED CODE COMPLIANCE BUT IF YOU STATE
 YOU ARE DESIGNING TO -70.6PSF, ANCHOR SPACING MUST
 COMPLY.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU NEED ASSISTANCE.
  