Plan Review Notes For Permit 08100237 |
Permit Number |
08100237 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2008-12-03 15:16:08 | COURTESY PARTIAL REVIEW | | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2004 | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL | | | | THIS IS A CURSORY REVIEW; LIST MAY NOT BE COMPLETE | | | | 1. SEE SHEET 6, 2 1/2" EDGE DISTANCE REQUIRES A FACTOR | | OF .71. 9" SPACING HAS BEEN CIRCLED ON THE PRODUCT | | APPROVAL, 9 X .71 = 6.39, BUT INSTALLATION SCHEDULE | | SPECIFIES 7.74. SEE OTHER COMMENTS REGARDING ANCHOR | | SPACING. | | | | 2. SHUTTER CONNECTION MOUNTING TYPE SHOULD CORRELATE | | WITH THE ANCHOR CHART. YOU'VE CIRCLED ANCHOR SPACING IN | | COLUMN "D", BUT HAVE SPECIFIED P-P3, NOT SURE WHAT THAT | | MEANS IN RELATION TO THE ANCHOR CHARTS. | | | | 3. A DESIGN PRESSURE OF -70.6 HAS BEEN SPECIFIED, | | SHOULD USE THE ROW FOR 60 - 100. HOWEVER -70.6 IS VERY | | HIGH FOR A 15' STRUCTURE LOCATED IN EXPOSURE B. IT IS | | ACCEPTABLE TO EXCEED CODE COMPLIANCE BUT IF YOU STATE | | YOU ARE DESIGNING TO -70.6PSF, ANCHOR SPACING MUST | | COMPLY. | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU NEED ASSISTANCE. | | |
|