2008-11-12 14:05:51****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
  
  
 1. SEE SHEET 6, SPACING IS FOR 3" EDGE DISTANCE. 2"
 EDGE DISTANCE REQUIRES A FACTOR OF .5.
  
 2. PLEASE CLARIFY HOW YOU HAVE DETERMINED 3000PSI
 CONCRETE STRENGTH. IT STATES THAT A TEST WAS PERFORMED.
 PLEASE INDICATE WHICH TESTING METHOD WAS USED. FBC
 R301.
  
 2ND REVIEW, NOT ADDRESSED. PUTTING A TAPCON INTO
 CONCRETE DOES NOT PROVIDE INFORMATION REGARDING THE
 STRENGTH OF THE CONCRETE.
  