2008-10-16 09:23:00 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBC FLORIDA BUILDING CODE 2004 |
| FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| CODE |
| FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL |
| FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| FAC FLORIDA ADMINISTRATIVE CODE |
| FS FLORIDA STATUTE |
| |
| 1. USE OF REMOVABLE IMPACT PROTECTION ON COMMERCIAL |
| BUILDINGS IS TO BE APPROVED BY THE BUILDING OFFICIAL |
| THROUGH A PRESTORM PREPARATION PLAN; SEE WIND-BORNE |
| DEBRIS IMPLEMENTATION STANDARD, ITEM 13. IMPACT ON THE |
| SECOND FLOOR IS GENERALLY REQUIRED. HTTP://WWW.CITYOFWP |
| B.COM/CONSTRUCTION/PDF/WIND-BORNE_DEBRIS_IMPLEMETATION. |
| PDF |
| |
| THIS DOCUMENT IS ALSO AVAILABLE IN THE LOBBY OF |
| CONSTRUCTION SERVICES. |
| |
| 2. IF USE OF REMOVABLE STORM PANELS IS APPROVED, AN |
| INSTALLATION SCHEDULE IS REQUIRED TO DEMONSTRATE |
| COMPLIANCE WITH FBC R301 (WIND). TWO SETS REQUIRED. HTT |
| P://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_INS |
| TALLATION.PDF |
| |
| 3. THE ELECTRIC PERMIT 07010976 FOR THIS PROPERTY (AND |
| ASSOCIATED WITH WORK FOR THIS PERMIT), IS EXPIRED. |
| PLEASE ADVISE AS TO STATUS. NOTE THAT THIS IS AN |
| APPLICATION TO REPAIR SHEETROCK ASSOCIATED WITH THE |
| ELECTRIC PERMIT. |
| |
| 4. THE PERMIT APPLICATION SCOPE INCLUDES REPAIR OF A |
| STAIRWAY. PROVIDE A STRUCTURAL DETAIL AND SITE PLAN |
| WHICH CLEARLY SHOWS SCOPE, LOCATION, AND METHOD OF |
| REPAIR, FBC*106, FBC R301. |
| |
| 5. DECLARE GOVERNING CODE, INCLUDING 2007 |
| REVISIONS/SUPPLEMENTS. |
| |
| 6. DECLARE WIND DESIGN CRITERIA, FBC R301. |
| |
| 7. DECLARE LEVEL OF ALTERATION FBC EB 301.5. |
| |
| 8. STRUCTURAL DETAILS PREPARED BY AN ENGINEER WERE |
| SUBMITTED. THIS IS NOT INCLUDED IN THE SCOPE OF WORK ON |
| THE APPLICATION. IT IS NOT CLEAR WHY THESE DETAILS HAVE |
| BEEN PROVIDED. THE DETAIL STATES THAT THE 2X4 IS "AS |
| NEEDED FOR REINFOCEMENT". REINFORCEMENT - STRUCTURAL |
| FOR THE WALL, OR BLOCKING FOR THE DRYWALL? THE |
| APPLICATION STATES "REPAIR SHEETROCK FOR UPDATED |
| ELECTRICAL". CLARIFY EXTENT OF DRYWALL REPAIR. |
| |
| 9. INSULATION IS NOT SHOWN, WALL AND TENANT SEPARATION |
| (FLOOR/CEILING), FBC13. AS SCOPE IS NOT CLEAR, |
| COMPLIANCE AND REQUIREMENTS NOT CLEAR AT THIS TIME. |
| |
| |
| |
| |
| |