Plan Review Notes
Plan Review Notes For Permit 08100178
Permit Number 08100178
Review Stop B
Sequence Number 1
Notes
Date Text
2008-10-16 09:23:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. USE OF REMOVABLE IMPACT PROTECTION ON COMMERCIAL
 BUILDINGS IS TO BE APPROVED BY THE BUILDING OFFICIAL
 THROUGH A PRESTORM PREPARATION PLAN; SEE WIND-BORNE
 DEBRIS IMPLEMENTATION STANDARD, ITEM 13. IMPACT ON THE
 SECOND FLOOR IS GENERALLY REQUIRED. HTTP://WWW.CITYOFWP
 B.COM/CONSTRUCTION/PDF/WIND-BORNE_DEBRIS_IMPLEMETATION.
 PDF
  
 THIS DOCUMENT IS ALSO AVAILABLE IN THE LOBBY OF
 CONSTRUCTION SERVICES.
  
 2. IF USE OF REMOVABLE STORM PANELS IS APPROVED, AN
 INSTALLATION SCHEDULE IS REQUIRED TO DEMONSTRATE
 COMPLIANCE WITH FBC R301 (WIND). TWO SETS REQUIRED. HTT
 P://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_INS
 TALLATION.PDF
  
 3. THE ELECTRIC PERMIT 07010976 FOR THIS PROPERTY (AND
 ASSOCIATED WITH WORK FOR THIS PERMIT), IS EXPIRED.
 PLEASE ADVISE AS TO STATUS. NOTE THAT THIS IS AN
 APPLICATION TO REPAIR SHEETROCK ASSOCIATED WITH THE
 ELECTRIC PERMIT.
  
 4. THE PERMIT APPLICATION SCOPE INCLUDES REPAIR OF A
 STAIRWAY. PROVIDE A STRUCTURAL DETAIL AND SITE PLAN
 WHICH CLEARLY SHOWS SCOPE, LOCATION, AND METHOD OF
 REPAIR, FBC*106, FBC R301.
  
 5. DECLARE GOVERNING CODE, INCLUDING 2007
 REVISIONS/SUPPLEMENTS.
  
 6. DECLARE WIND DESIGN CRITERIA, FBC R301.
  
 7. DECLARE LEVEL OF ALTERATION FBC EB 301.5.
  
 8. STRUCTURAL DETAILS PREPARED BY AN ENGINEER WERE
 SUBMITTED. THIS IS NOT INCLUDED IN THE SCOPE OF WORK ON
 THE APPLICATION. IT IS NOT CLEAR WHY THESE DETAILS HAVE
 BEEN PROVIDED. THE DETAIL STATES THAT THE 2X4 IS "AS
 NEEDED FOR REINFOCEMENT". REINFORCEMENT - STRUCTURAL
 FOR THE WALL, OR BLOCKING FOR THE DRYWALL? THE
 APPLICATION STATES "REPAIR SHEETROCK FOR UPDATED
 ELECTRICAL". CLARIFY EXTENT OF DRYWALL REPAIR.
  
 9. INSULATION IS NOT SHOWN, WALL AND TENANT SEPARATION
 (FLOOR/CEILING), FBC13. AS SCOPE IS NOT CLEAR,
 COMPLIANCE AND REQUIREMENTS NOT CLEAR AT THIS TIME.
  
  
  
  
  