 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 SAME COMMENTS AS THE PREVIOIS REVIEW
  
 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND 471
 FS, RESPECTIVELY.
 THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL
 IF EXEMPTIONS UNDER CHAPTER 471.003, FLORIDA STATUTES,
 IF EXEMPTIONS APPLY.*** THIS COMMENT IS IN REFERENCE TO
 THE SHEETS SUBMITTED LABELED "SUNPOWER" AND "SUNWIZE"
 THAT DO NOT CONTAIN A PRINTED AND SIGNED NAME FOR THE
 PERSON RESPONSIBILITY FOR THE DESIGN.
  
 RESPOND TO REVIEW COMMENTS IN WRITING.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/805-6718