Plan Review Notes For Permit 08100010 |
Permit Number |
08100010 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-10-23 11:11:38 | ***DENIED*** | | | | 1) EQUIPMENT PROTECTION MAY BE REQUIRED IF THE | | POSSIBILITY OF MECHANICAL DAMAGE EXISTS. | | | | 2) IN ADDITION TO NFPA 101, 2003, WORK SHALL COMPLY | | WITH NFPA 110, STANDARD FOR EMERGENCY POWER AND STANDBY | | SYSTEMS. | | | | 3) WHAT BUILDING EQUIPMENT AND OR LIFE SAFETY SYSTEMS | | WILL BE TIED INTO THE GENEREATOR? | | | | 4) CLEARLY IDENTIFY THE LOCATION AND DIMENSIONS OF | | EXHAUST TERMINUS AS IT RELATES TO BUILDING OPENINGS. | | | | | | MIKE WENNERGREN, ASST. FIRE MARSHAL | | FIRE PLAN REVIEW | | FIRE PREVENTION (561) 804-4756 |
|