2008-10-23 11:11:38***DENIED***
  
 1) EQUIPMENT PROTECTION MAY BE REQUIRED IF THE
 POSSIBILITY OF MECHANICAL DAMAGE EXISTS.
  
 2) IN ADDITION TO NFPA 101, 2003, WORK SHALL COMPLY
 WITH NFPA 110, STANDARD FOR EMERGENCY POWER AND STANDBY
 SYSTEMS.
  
 3) WHAT BUILDING EQUIPMENT AND OR LIFE SAFETY SYSTEMS
 WILL BE TIED INTO THE GENEREATOR?
  
 4) CLEARLY IDENTIFY THE LOCATION AND DIMENSIONS OF
 EXHAUST TERMINUS AS IT RELATES TO BUILDING OPENINGS.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW