Plan Review Notes For Permit 08100001 |
Permit Number |
08100001 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-10-06 08:36:17 | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 | | NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED, | | CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | 1} THE ADDRESS ON THE ENGINEERING REFERENCES THE WRONG | | LOCATION.AND PROJECT (COVER SHEET). | | | | 2} PAGE # 2 ON THE ENGINEERING CALCS REFERENCES | | 1606.1.1, A SECTION THAT DOES NOT EXIST IN THE 2004 | | FBC. SECTION 1609.1.1 WOULD BE THE CORRECT REFERENCE. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | |
|