Plan Review Notes For Permit 08090752 |
Permit Number |
08090752 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-10-14 17:01:05 | ROOF ALTERATION AND RE-ROOFING BUILDING REVIEW | | CHECKLIST. | | REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. | | | | 1- GENERAL CONTRACTOR IS NOT ALLOWED TO DO METAL | | ROOFING UNLESS GENERAL CONTRACTOR IS CERTIFIED OR | | REGISTERED AS A ROOFING CONTRACTOR. SEC. 489.113(3)(G) | | OF FLORIDA STATUTES. | | NEED ROOFING CONTRACTOR TO DO THE METAL RE-ROOFING. | | (NOTE: SEPARATE PERMIT IS REQUIRED FOR ROOFING WORK). | | | | 2- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE | | 9B-72 FOR THE METAL ROOFING TO BE INSTALLED. | | | | 3- ARCHITECT OF RECORD FOR THIS PERMIT NEEDS TO REVIEW | | AND APPROVE IN WRITING (NOT SIGNING AND SEALING) ALL | | PRODUCT APPROVALS AS REQUIRED BY SEC. 106.3.3 CITY | | AMENDMENTS TO FBC 2004. | | | | 4- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO | | LOW. SEC. 108.3 CITY AMENDMENTS TO FBC 2004. | | UPDATE VALUATION TO INCLUDE DESIGN PROFESSIONAL FEES | | AND CONTRACTOR'S OVERHEAD AND PROFIT, DEMOLITION AND | | NEW WORK TO BE PERFORMED. | | | | 5- SHEET A-1: | | A) UPDATE GENERAL NOTES: REFER TO FBC 2004 WITH 2007 | | REVISIONS, NOT 2006 REVISIONS. | | B) REVISE WIND DESIGN INFORMATION. PROPERTY IS LOCATED | | WEST OF I-95 NOT EAST. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|