Plan Review Notes
Plan Review Notes For Permit 08090752
Permit Number 08090752
Review Stop B
Sequence Number 1
Notes
Date Text
2008-10-14 17:01:05ROOF ALTERATION AND RE-ROOFING BUILDING REVIEW
 CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- GENERAL CONTRACTOR IS NOT ALLOWED TO DO METAL
 ROOFING UNLESS GENERAL CONTRACTOR IS CERTIFIED OR
 REGISTERED AS A ROOFING CONTRACTOR. SEC. 489.113(3)(G)
 OF FLORIDA STATUTES.
 NEED ROOFING CONTRACTOR TO DO THE METAL RE-ROOFING.
 (NOTE: SEPARATE PERMIT IS REQUIRED FOR ROOFING WORK).
  
 2- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR THE METAL ROOFING TO BE INSTALLED.
  
 3- ARCHITECT OF RECORD FOR THIS PERMIT NEEDS TO REVIEW
 AND APPROVE IN WRITING (NOT SIGNING AND SEALING) ALL
 PRODUCT APPROVALS AS REQUIRED BY SEC. 106.3.3 CITY
 AMENDMENTS TO FBC 2004.
  
 4- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. SEC. 108.3 CITY AMENDMENTS TO FBC 2004.
 UPDATE VALUATION TO INCLUDE DESIGN PROFESSIONAL FEES
 AND CONTRACTOR'S OVERHEAD AND PROFIT, DEMOLITION AND
 NEW WORK TO BE PERFORMED.
  
 5- SHEET A-1:
 A) UPDATE GENERAL NOTES: REFER TO FBC 2004 WITH 2007
 REVISIONS, NOT 2006 REVISIONS.
 B) REVISE WIND DESIGN INFORMATION. PROPERTY IS LOCATED
 WEST OF I-95 NOT EAST.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712