2008-09-30 16:30:26 | PLUMBING PLAN REVIEW: |
| DENIED: |
| |
| PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| |
| 1. PLEASE KNOW THAT THERE IS NO APPROVED PLUMBING ON |
| MASTER PERMIT #08070214, WHICH IS REFERENCED ON THE |
| PLUMBING PERMIT APPLICATION. PLEASE KNOW THAT MASTER |
| PERMIT #08070214 IS FOR STRUCTURAL ONLY. PLEASE KNOW |
| THAT ON SHEET 3 OF 3, ON MASTER PERMIT #08070214, IT |
| CLEARLY INDICATES IN FOUR PLACES THAT "ALL ELECTRICAL |
| AND PLUMBING WORK BY OTHERS". PLEASE SUBMIT PLANS FOR |
| THE PROPOSED PLUMBING WORK CLEARLY INDICATING THE |
| FOLLOWING REQUESTED INFORMATION COMPLIANT WITH THE |
| FBC-2004 PLUMBING CODE SECTIONS. |
| |
| A} PLEASE INDICATE THE LOCATION OF THE PROPOSED |
| PLUMBING WORK OF THE (2) DOCK PEDESTALS ON A SITE OR |
| SURVEY PLAN. CLEARLY INDICATE IF THE PROPOSED WORK IS |
| BEING INSTALLED TO AN EXISTING SYSTEM. CLEARLY INDICATE |
| THE POINT OF CONNECTION TO THE EXISTING (IF APPLICABLE) |
| SYSTEM. PER SECTION 601.1 SCOPE. |
| |
| B} PLEASE SUBMIT AN ISOMETRIC POTABLE WATER DIAGRAM |
| THAT CLEARLY INDICATES THE PIPE MATERIAL, PIPE SIZES, |
| VALVE LOCATIONS, RPZV BACKFLOW PREVENTER LOCATION |
| (CLEARLY INDICATE IF THE RPZV BACK FLOW PREVENTER IS |
| EXISTING OR NEW) AND HOW THE PIPING WILL BE SUPPORTED. |
| PER SECTION 601.1 SCOPE AND (W.P.B. AS AMENDED) SECTION |
| 106.3.5.1.3 PLUMBING (3), (8), (10), AND (13). |
| |
| 2. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING |
| DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE |
| PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE |
| ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER |
| SECTION *106.3.4.3. |
| IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR ENGINEER, |
| THEN HE OR SHE SHALL AFFIX HIS OR HER OFFICIAL SEAL, |
| SIGNATURE AND DATE TO SAID DRAWINGS, PER FLORIDA |
| STATUTES 481 AND 471 RESPECTIVELY. |
| |
| END OF COMMENTS: |
| |
| REVIEW BY: MIKE PERSON |
| PLUMBING PLANS EXAMINER |
| (561) 805-6730 |
| FAX (561) 805-6731 |
| E-MAIL: [email protected] |