Plan Review Notes For Permit 08090691 |
Permit Number |
08090691 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2008-11-20 11:57:25 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 | | RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1 | | AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | THESE ARE REPEAT COMMENTS | | | | 1} SHOW THE LOCATION OF THE A/C EQUIPMENT ON THE PLAN. | | ALSO SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER | | 440.14, RECEPTACLE PER 210.63, LIGHT PER 210.70(A) (3), | | IF REQUIRED***NO RECEPTACLE LOCATION IS SHOWN, IF | | WHITHIN 25 FEET A NOTE ON THE PLAN WILL SUFFICE. | | | | NEW COMMENT | | | | 2} INDICATE THE FEED SIZE AND OCPFOR THE AHU AND | | CONDENSING UNIT.. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | |
|