2008-11-19 16:10:06 | DENIED |
| REFERENCE: FBC-2004 FUEL GAS |
| |
| 1. A SEPARATE GAS PERMIT IS REQUIRED. SUBMIT THE |
| FOLLOWING INFORMATION FOR PERMIT: |
| |
| A. OK |
| |
| B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2004 FUEL GAS CODE SEC 402.2. |
| ****RESPONSE NOTED, BUT THE MANUF. SHEETS FOR THE WOK |
| DOES NOT REFLECT THE BTU LOAD INDICATED ON THE GAS LOAD |
| CALCULATIONS. PLEASE INDICATE WHICH MODEL WILL BE USED |
| AND SHOW THAT THE BTU LOAD REFLECTS THE GAS LOAD |
| CALCULATIONSL. NO MANUF. SHEETS SUBMITTED FOR THE GAS |
| WATER HEATER. |
| |
| C. OK |
| |
| D. SUBMIT THE MANUF. SPECIFICATION SHEETS FOR THE |
| REGULATOR. SHEETS SHALL SHOW A LISTING AND INDICATED |
| THE TOTAL BTU LOAD APPLICABLE FOR THE REGULATOR MODEL. |
| INDICATE MODEL. |
| ****RESPONSE NOTED, BUT NO LISTING IS INDICATED AND NO |
| 1-1/2" OUTLET IS INDICATED ON ANY MODEL. INDICATE THE |
| MODEL NUMBER, (MUST SHOW 1-1/2" OUTLET), AND HIGHLIGHT |
| THE MAXIMUM CAPACITY FOR THE REGULATOR FOR MULTIPLE |
| APPLIANCES. |
| |
| E. OK |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |