Date |
Text |
2008-10-02 10:55:47 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 FUEL GAS |
| FBC-2004 CHAPTER 1 |
| CITY WPB MUNICIPAL CODE |
| |
| 1. SHT C-1 GENERAL NOTES #1 TO INCLUDE 2005, 2006 & |
| 2007 REVISIONS/AMENDMENTS TO THE 2004 FLORIDA BUILDING |
| CODE AND THE JURISDICATION OF AUTHORITY IS THE CITY OF |
| WEST PALM BEACH, NOT ROYAL PALM BEACH. PLEASE UPDATE |
| GENERAL NOTE #1. SECTION 106.1.3. |
| |
| 2. SHT 1.1A EQUIPMENT SCHEDULE. PLEASE CLARIFY THE |
| FOLLOWING: |
| ITEM NO. 4 MOP SINK SHOWS NO WATER SUPPLIES NOR DRAIN. |
| ITEM BETWEEN 9 & 10 SHOWS 1/2" WATER SUPPLIES BUT SHOWS |
| NO ITEM. |
| ITEM NO. 15 HAND SINKS SHOWS NO WATER SUPPLIES NOR |
| DRAIN. |
| ITEM NO. 30 HAND SINK SHOWS NO WATER SUPPLIES NOR |
| DRAIN. |
| ITEM BETWEEN 31 & 32 SHOWS 3/4" INDIRECT WASTE BUT NO |
| ITEM. |
| SECTIONS 106.1.1, 601.1 & 701.1. |
| |
| 3. SHT 3.0P SANITARY RISER. DISH WASHER SHALL DRAIN |
| INTO THE SANITARY SYSTEM, NOT THE GREASE SYSTEM. |
| ARTICLE III SECTION 90-124(7)(B). |
| |
| 4. SHT 3.0P SANITARY RISER SHALL BE LABELED AS THE |
| GREASE RISER DIAGRAM. FIXTURE SHOWN TO THE RIGHT OF THE |
| TRENCH DRAIN SHALL BE IDENTIFIED, (INDICATED AS |
| "STUDOR"). |
| |
| 5. THE GREASE INTERCEPTOR SHALL BE SIZED BY THE UTILITY |
| DEPARTMENT, INDUSTRIAL PRETREATMENT. PLEASE CONTACT |
| HOLLY MCGRATH LABORATORY SUPERVISOR BY PHONE AT (561) |
| 822-2271, OR BY FAX AT (561) 822-2279, OR BY E-MAIL AT |
| [email protected]. A WRITTEN DETERMINATION OR E-MAIL |
| FROM ENVIRONMENTAL COMPLIANCE IS REQUIRED. ARTICLE III |
| SECTION 90-124(7). |
| |
| 6. SHT P3.0P PLUMBING PLAN. EXPLAIN THE SANITARY LINE |
| SHOWN PAST THE FLOOR SINK TO THE 3 COMPARTMENT SINK. |
| SECTIONS 106.1.1, 701.1 & 901.1. |
| |
| 7. SHT 3.0P PLUMBING PLAN SHOWS NO WATER SUPPLY PIPING |
| TO THE 3 COMPARTMENT SINK & SHOWS 2 HOT SUPPLY LINES TO |
| THE HAND SINK. PLEASE CORRELATE WITH RISER DIAGRAM. |
| SECTIONS 106.1.1 & 601.1. |
| |
| 8. SHT 3.2P WATER RISER DIAGRAM DOES NOT REFLECT THE |
| FLOOR PLAN. THE TOILET ROOM W/C & LAV SHOWN ON THE |
| RIGHT SIDE OF THE TENANT SUPPLY LINE ON THE PLUMBING |
| PLAN IS SHOWN ON THE LEFT SIDE OF THE TENANT SUPPLY |
| LINE ON THE RISER DIAGRAM. THE SUPPLY LINE TO THE W/C |
| IN THE OTHER TOILET ROOM IS NOT SHOWN ON THE RISER |
| DIAGRAM. IDENTIFY THE LAV IN THE SECOND BATH. THE HAND |
| SINK NEXT TO THE WOK SHOWS 2 HOT SUPPLY LINES. THE GATE |
| VALVE AND SUBMETER INDICATED ON THE RISER DIAGRAM IS |
| NOT SHOWN ON THE PLUMBING PLAN. PLEASE CORRELATE. |
| SECTIONS 106.1.1 & 106.1. |
| |
| 9. A SEPARATE GAS PERMIT IS REQUIRED. SUBMIT THE |
| FOLLOWING INFORMATION FOR PERMIT: |
| |
| A. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES A.3.1(4). THIS IS REQUIRED FOR THE 2 |
| PSI SYSTEM AND THE .5 PSI SYSTEMS. |
| |
| B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2004 FUEL GAS CODE SEC 402.2. |
| |
| C. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| VALVE TO BE BELOW CEILING. MANUAL SHUT |
| OFF VALVE TO BE UPSTREAM. UNION TO BE |
| DOWN STREAM OF MANUAL VALVE. THIS IS ALSO REQUIRED FOR |
| THE S.O.V AND REGULATOR. A UNION IS REQUIRED AND ALL |
| SHALL BE INSTALLED BELOW THE CEILING. |
| |
| D. SUBMIT THE MANUF. SPECIFICATION SHEETS FOR THE |
| REGULATOR. SHEETS SHALL SHOW A LISTING AND INDICATED |
| THE TOTAL BTU LOAD APPLICABLE FOR THE REGULATOR MODEL. |
| INDICATE MODEL. |
| |
| E. MINIMUM SIZE 1" REQUIRED TO THE RANGE. 3/4" IS |
| INDICATED IN GAS LOAD CALCULATIONS. TABLE 402.4(2). |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |
| |