Plan Review Notes
Plan Review Notes For Permit 08090682
Permit Number 08090682
Review Stop P
Sequence Number 1
Notes
Date Text
2008-10-02 10:55:47DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 CITY WPB MUNICIPAL CODE
  
 1. SHT C-1 GENERAL NOTES #1 TO INCLUDE 2005, 2006 &
 2007 REVISIONS/AMENDMENTS TO THE 2004 FLORIDA BUILDING
 CODE AND THE JURISDICATION OF AUTHORITY IS THE CITY OF
 WEST PALM BEACH, NOT ROYAL PALM BEACH. PLEASE UPDATE
 GENERAL NOTE #1. SECTION 106.1.3.
  
 2. SHT 1.1A EQUIPMENT SCHEDULE. PLEASE CLARIFY THE
 FOLLOWING:
 ITEM NO. 4 MOP SINK SHOWS NO WATER SUPPLIES NOR DRAIN.
 ITEM BETWEEN 9 & 10 SHOWS 1/2" WATER SUPPLIES BUT SHOWS
 NO ITEM.
 ITEM NO. 15 HAND SINKS SHOWS NO WATER SUPPLIES NOR
 DRAIN.
 ITEM NO. 30 HAND SINK SHOWS NO WATER SUPPLIES NOR
 DRAIN.
 ITEM BETWEEN 31 & 32 SHOWS 3/4" INDIRECT WASTE BUT NO
 ITEM.
 SECTIONS 106.1.1, 601.1 & 701.1.
  
 3. SHT 3.0P SANITARY RISER. DISH WASHER SHALL DRAIN
 INTO THE SANITARY SYSTEM, NOT THE GREASE SYSTEM.
 ARTICLE III SECTION 90-124(7)(B).
  
 4. SHT 3.0P SANITARY RISER SHALL BE LABELED AS THE
 GREASE RISER DIAGRAM. FIXTURE SHOWN TO THE RIGHT OF THE
 TRENCH DRAIN SHALL BE IDENTIFIED, (INDICATED AS
 "STUDOR").
  
 5. THE GREASE INTERCEPTOR SHALL BE SIZED BY THE UTILITY
 DEPARTMENT, INDUSTRIAL PRETREATMENT. PLEASE CONTACT
 HOLLY MCGRATH LABORATORY SUPERVISOR BY PHONE AT (561)
 822-2271, OR BY FAX AT (561) 822-2279, OR BY E-MAIL AT
 [email protected]. A WRITTEN DETERMINATION OR E-MAIL
 FROM ENVIRONMENTAL COMPLIANCE IS REQUIRED. ARTICLE III
 SECTION 90-124(7).
  
 6. SHT P3.0P PLUMBING PLAN. EXPLAIN THE SANITARY LINE
 SHOWN PAST THE FLOOR SINK TO THE 3 COMPARTMENT SINK.
 SECTIONS 106.1.1, 701.1 & 901.1.
  
 7. SHT 3.0P PLUMBING PLAN SHOWS NO WATER SUPPLY PIPING
 TO THE 3 COMPARTMENT SINK & SHOWS 2 HOT SUPPLY LINES TO
 THE HAND SINK. PLEASE CORRELATE WITH RISER DIAGRAM.
 SECTIONS 106.1.1 & 601.1.
  
 8. SHT 3.2P WATER RISER DIAGRAM DOES NOT REFLECT THE
 FLOOR PLAN. THE TOILET ROOM W/C & LAV SHOWN ON THE
 RIGHT SIDE OF THE TENANT SUPPLY LINE ON THE PLUMBING
 PLAN IS SHOWN ON THE LEFT SIDE OF THE TENANT SUPPLY
 LINE ON THE RISER DIAGRAM. THE SUPPLY LINE TO THE W/C
 IN THE OTHER TOILET ROOM IS NOT SHOWN ON THE RISER
 DIAGRAM. IDENTIFY THE LAV IN THE SECOND BATH. THE HAND
 SINK NEXT TO THE WOK SHOWS 2 HOT SUPPLY LINES. THE GATE
 VALVE AND SUBMETER INDICATED ON THE RISER DIAGRAM IS
 NOT SHOWN ON THE PLUMBING PLAN. PLEASE CORRELATE.
 SECTIONS 106.1.1 & 106.1.
  
 9. A SEPARATE GAS PERMIT IS REQUIRED. SUBMIT THE
 FOLLOWING INFORMATION FOR PERMIT:
  
 A. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). THIS IS REQUIRED FOR THE 2
 PSI SYSTEM AND THE .5 PSI SYSTEMS.
  
 B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 C. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE. THIS IS ALSO REQUIRED FOR
 THE S.O.V AND REGULATOR. A UNION IS REQUIRED AND ALL
 SHALL BE INSTALLED BELOW THE CEILING.
  
 D. SUBMIT THE MANUF. SPECIFICATION SHEETS FOR THE
 REGULATOR. SHEETS SHALL SHOW A LISTING AND INDICATED
 THE TOTAL BTU LOAD APPLICABLE FOR THE REGULATOR MODEL.
 INDICATE MODEL.
  
 E. MINIMUM SIZE 1" REQUIRED TO THE RANGE. 3/4" IS
 INDICATED IN GAS LOAD CALCULATIONS. TABLE 402.4(2).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved