Plan Review Notes
Plan Review Notes For Permit 08090682
Permit Number 08090682
Review Stop G
Sequence Number 1
Notes
Date Text
2008-10-02 10:59:18DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 1. A SEPARATE GAS PERMIT IS REQUIRED. SUBMIT THE
 FOLLOWING INFORMATION FOR PERMIT:
  
 A. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). THIS IS REQUIRED FOR THE 2
 PSI SYSTEM AND THE .5 PSI SYSTEMS.
  
 B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 C. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE. THIS IS ALSO REQUIRED FOR
 THE S.O.V AND REGULATOR. A UNION IS REQUIRED AND ALL
 SHALL BE INSTALLED BELOW THE CEILING.
  
 D. SUBMIT THE MANUF. SPECIFICATION SHEETS FOR THE
 REGULATOR. SHEETS SHALL SHOW A LISTING AND INDICATED
 THE TOTAL BTU LOAD APPLICABLE FOR THE REGULATOR MODEL.
 INDICATE MODEL.
  
 E. MINIMUM SIZE 1" REQUIRED TO THE RANGE. 3/4" IS
 INDICATED IN GAS LOAD CALCULATIONS. TABLE 402.4(2).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  